- 2068 Chaitra · 8 marks
Sequence networks decoupled for static circuit
Short answer
The sequence impedance matrix of a symmetrical static circuit is diagonal, with zero off-diagonal terms, because transforming the balanced Zp yields Z0 = Zs+2Zm, Z1 = Z2 = Zs−Zm. Thus each sequence current produces voltage drop only in its own network, leaving them fully decoupled.
For a 3-phase symmetrical static circuit, justify that sequence networks are decoupled.
For a three-phase symmetrical static circuit (line, transformer, static load), the impedance matrix in sequence quantities is diagonal, so a current of one sequence produces voltage drops of that sequence only; this means the three sequence networks are decoupled.
Phase equations
Each phase has self impedance and equal mutual impedance to each other phase:
Transformation
With , :
where
First find , column by column (using ):
- Column 1: each row , so column
- Column 2: rows times
- Column 3: rows times
So ; the columns of are eigenvectors of . Therefore
Result
with and .
All off-diagonal (mutual) terms between sequences are zero, so:
- Positive sequence current causes only positive sequence voltage drop, and similarly for negative and zero.
- Each sequence network can be drawn and solved independently as a single-phase circuit.
- The networks are connected to each other only at points of unbalance (fault points), which is the basis of unsymmetrical fault analysis.
If the circuit is not symmetrical (e.g. unequal mutual impedances in an untransposed line), off-diagonal terms appear and the sequence networks become coupled.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- SLG fault: sequence networks in series · Power System Analysis II, chapter 5 · asked 5×
- Sequence components decoupled for power flow · Power System Analysis II, chapter 4
- Sequence networks with parallel transformer banks · Power System Analysis II, chapter 4
- Sequence networks of Y load, neutral current · Power System Analysis II, chapter 4 · asked 2×
- 3-phase power in symmetrical components · Power System Analysis II, chapter 4 · asked 3×
- Initial symmetrical current, load short circuit · Power System Analysis II, chapter 3
- Bridge single-phase cycloconverter conduction sequence · Power Electronics, chapter 6 · asked 3×
- Phase sequence and significance · Basic Electrical Engineering, chapter 8
- DFRT and equivalent circuit of single phase IM · Electric Machines II, chapter 3
- Determining single phase IM equivalent circuit parameters · Electric Machines II, chapter 3