- 2076 Bhadra · 6 marks
Differential protection: 11 kV, 100 MVA generator
Short answer
Primary operating current = 1×200 = 200 A; Vph = 6351 V. Unprotected fraction = (200×6)/6351 = 0.189. Thus 81.1% of the winding is protected.
A 11 kV, 100 MVA generator is grounded through a resistance of 6 Ω. The CTs have a ratio of 1000/5. The relay is set to operate when there is an out of balance current of 1 A. What percentage of the generator winding will be protected by percentage differential scheme of protection?
In a differential scheme, an earth fault at fraction x of the winding from the neutral gives a fault current x·V_ph / R_n. The relay sees this as out-of-balance current; the part of the winding near the neutral, where the fault current is below the setting, is unprotected.
Data: 11 kV, 100 MVA; R_n = 6 Ω; CT 1000/5 (ratio 200); relay setting 1 A; winding impedance neglected.
I_op (primary) = 1 × 200 = 200 A
V_ph = 11 000 / √3 = 6350.85 V
x = I_op × R_n / V_ph
= 200 × 6 / 6350.85
= 0.1890 (unprotected)
Protected = 1 − 0.1890 = 0.8110
Earth ──R_n=6Ω── N ──[ 18.9% ]──[ 81.1% ]── line
unprotected protected
Answer: about 81.1% of the generator winding is protected; the 18.9% nearest the neutral is unprotected.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Earth fault protection: 20 MVA alternator · Switchgear and Protection, chapter 7
- Percentage differential relay: 150 MVA transformer · Switchgear and Protection, chapter 7
- Percentage differential relay: 125 MVA transformer · Switchgear and Protection, chapter 7
- Balanced circulating current: 10 kV alternator · Switchgear and Protection, chapter 7
- CT ratio and connection for 11/132 kV · Switchgear and Protection, chapter 7
- Percentage bias in differential relay · Switchgear and Protection, chapter 7
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Per unit values: 100 MVA generator, two motors · Power System Analysis I, chapter 3