Earth fault protection: 20 MVA alternator
Short answer
Primary operating current = 1.5×200 = 300 A; Vph = 6351 V. Unprotected = (300×5)/6351 = 0.236, so protected = 76.4%. For 90% protection, earthing resistance cannot exceed 0.10×6351/300 = 2.12 Ω.
The neutral point of a three-phase 20 MVA, 11 kV alternator is earthed through a resistance of 5 Ω, the relay is set to operate when there is an out of balance current of 1.5 A. The CTs have a ratio 1000/5. What percentage of winding is protected against an earth fault and what should be the minimum value of earthing resistance to protect 90% of the winding?
For an earth fault at fraction x of the winding from the neutral, the fault current is x·V_ph / R_n (winding impedance neglected). The relay operates when the corresponding CT secondary current reaches the setting.
Data: 20 MVA, 11 kV, star; R_n = 5 Ω; relay setting 1.5 A; CT 1000/5 (ratio 200).
Step 1: Primary operating current
I_op (primary) = 1.5 × 200 = 300 A
V_ph = 11 000 / √3 = 6350.85 V
Step 2: Percentage of winding protected
x × V_ph / R_n = I_op
x = 300 × 5 / 6350.85 = 0.2362 (unprotected)
Protected = 1 − 0.2362 = 0.7638 → 76.38%
Step 3: Earthing resistance to protect 90%
To protect 90%, only x = 0.10 may be unprotected:
0.10 × V_ph / R = 300
R = 0.10 × 6350.85 / 300 = 2.117 Ω
Any resistance larger than this leaves more than 10% unprotected, so 2.117 Ω is the limiting (maximum permissible) value of earthing resistance; a lower resistance protects more winding but gives larger earth fault currents.
Answer: 76.38% of the winding is protected; earthing resistance must be 2.117 Ω (not more) to protect 90% of the winding.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Differential protection: 11 kV, 100 MVA generator · Switchgear and Protection, chapter 7
- Balanced circulating current: 10 kV alternator · Switchgear and Protection, chapter 7
- Pilot current with tap change (10 MVA) · Switchgear and Protection, chapter 7
- Merz-Price: protected winding (13.8 kV) · Switchgear and Protection, chapter 7 · asked 2×
- IDMT settings for 20 MVA transformer and feeder · Switchgear and Protection, chapter 7 · asked 2×
- Combined phase and earth fault protection of generator · Switchgear and Protection, chapter 7
- L-L fault line voltages, 25 MVA alternator · Power System Analysis II, chapter 5 · asked 2×
- Neutral reactance/resistance to limit L-G current · Power System Analysis II, chapter 5
- Fault MVA at bus 5 with inductive lines · Power System Analysis II, chapter 3 · asked 2×
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×