Pilot current with tap change (10 MVA)

Short answer

LV CT ratio is N = 75 x (132/33)/√3 = 173.2 : 1, star connected. At 128 kV tap and 5 times full load, LV pilot current is 874.77/173.2 = 5.05 A, HV pilot current is √3 x 225.53/75 = 5.21 A, giving 0.158 A relay unbalance.

A 10 MVA, 132/33 kV, star-delta, three-phase, 50 Hz transformer is connected in delta on the low voltage side and in star with star point earthed on the high voltage side. If the CTs on the high voltage have a ratio of 75/1 A, determine the CT ratio on the low voltage side. What would be the current circulating through pilots for a through fault due to which a current of 5 times the full load occurs if the voltage tapping is set to 128 kV at the time of occurrence of fault?

HV is star connected, so the HV CTs are connected in delta; LV is delta connected, so the LV CTs are connected in star. The LV CT ratio is chosen so that pilot currents balance at the nominal ratio 132/33 kV. A tap change upsets this balance and a spill current flows.

Data: 10 MVA, 132/33 kV; HV CTs 75/1 (in delta); through fault = 5 × full load; tap set at 128 kV.

Step 1: LV CT ratio

For HV current I_H, the delta of HV CTs gives a pilot current √3 I_H / 75. The LV CTs (ratio N:1, star) give I_L / N, with I_L = 4 I_H (132/33).

I_L / N = √3 I_H / 75
N = 75 × (I_L/I_H) / √3 = 75 × 4 / √3 = 173.2
LV CT ratio = 173.2 : 1

Step 2: Fault currents with 128 kV tap

Full-load current on the LV (33 kV) side:

I_FL(LV) = 10 × 10⁶ / (√3 × 33 × 10³) = 174.95 A
Through-fault LV current = 5 × 174.95 = 874.77 A
HV current with tap at 128 kV = 874.77 × 33/128 = 225.53 A

Step 3: Pilot currents

From LV CTs: 874.77 / 173.2 = 5.051 A
From HV CTs: √3 × 225.53 / 75 = 5.208 A
Out-of-balance (relay) current = 5.208 − 5.051 = 0.158 A

Answer: LV CT ratio = 173.2 : 1 (star connected). For the through fault with the tap at 128 kV, the pilot currents are about 5.05 A (LV side) and 5.21 A (HV side), so an unbalanced current of 0.158 A circulates through the relay. A percentage-biased relay is needed so that this does not cause tripping. (If "5 times full load" is taken on the HV side, the corresponding values are 5.05 A, 4.90 A and 0.153 A.)