Combined phase and earth fault protection of generator

Short answer

Neutral and line-end CTs are star-connected with pilot wires. Phase-fault relays are connected between the pilots and a common star point; an earth-fault relay connects from that point to the CT neutral. Phase faults produce unbalance in phase relays; earth faults cause residual current in the earth relay.

Draw the connection diagram of combined phase fault and earth fault protection scheme applied to the generator.

In the combined phase and earth fault protection scheme, a single set of CTs on each side of the generator winding feeds a differential (Merz-Price) scheme for phase faults and, through the residual (neutral) connection of the same pilots, an earth fault relay. This saves CTs and covers both types of fault.

Connection diagram

 Neutral-side CTs      Stator         Line-side CTs
  (CT)──────────────── R ───────────────(CT)
  (CT)──────────────── Y ───────────────(CT)
  (CT)──────────────── B ───────────────(CT)
   │││   star pt                         │││
   │││     │                             │││
   │││   R_n (earthing)                  │││
   │││     ⏚                             │││
   ││└───── pilot B ──────┬───────────────┘││
   │└────── pilot Y ──────┼──┬─────────────┘│
   └─────── pilot R ──────┼──┼──┬───────────┘
                         [P][P][P]  phase relays
                          │  │  │  (87)
                          └──┴──┴───[E]── neutral
                                  earth fault
                                  relay (64)

Arrangement

  • Identical CTs at the neutral end and the line end of each phase; the two CT groups are each connected in star.
  • Pilot wires join corresponding phases, forming a circulating-current loop.
  • Two (or three) phase-fault relays (P) are connected between the pilots and a common star point.
  • An earth-fault relay (E) is connected between this common point and the star point of the CTs (neutral pilot), so it carries the residual current.

Operation

  • Normal and external faults: currents at both ends are equal, the secondary currents circulate and no current flows in any relay.
  • Phase-to-phase fault inside the winding: the out-of-balance current returns through the phase relays of the faulted phases, which trip.
  • Earth fault inside the winding: the unbalance current returns through the earth-fault relay (with a lower setting), giving sensitive earth fault protection.
  • The relays trip the generator breaker, field breaker and prime mover.

✓ Answer checked by Claude Opus 5.5 (high effort)