Restricted earth fault protection
Short answer
Restricted earth fault (REF) is a sensitive unit protection for earth faults within a star winding. It compares residual current of phase CTs with neutral CT current; for internal faults, difference flows to relay. High-impedance relay stabilises against CT saturation. Used on HV star winding of GSU transformers and small resistance-earthed generators.
What is restricted earth fault protection? Illustrate its use with suitable diagram.
Restricted earth fault (REF) protection is a sensitive unit protection that detects earth faults inside a defined zone only, usually a star-connected transformer or generator winding. It compares the sum of the three phase currents with the neutral current.
Principle
- CTs are placed in each phase and in the neutral-to-earth connection, all of the same ratio.
- The three phase CTs are connected in parallel (residual connection) and then in parallel with the neutral CT, with a relay across them.
- External earth fault (outside the zone): the residual current from the phase CTs equals the neutral CT current, so they circulate between CTs and no current flows through the relay.
- Internal earth fault (inside the winding): the neutral current has no matching residual current, so the difference flows through the relay and it trips.
A ---[CT]-----+---- to system
B ---[CT]-----+
C ---[CT]-----+
Star | | | |
winding \ | / | residual
\|/ |
N ---+--[CT_N]---+---[ R ]--+
| relay |
earth (high-impedance, with
stabilising resistor
and Metrosil)
Features
- Usually a high-impedance relay with a stabilising resistor so CT saturation on heavy external faults does not cause false trips. A non-linear resistor (Metrosil) limits voltage during internal faults.
- Very sensitive: it covers faults close to the neutral end, where the ordinary transformer differential (87T) is not sensitive enough. On a resistance-earthed winding a fault near the neutral gives very little phase current.
- Fast and stable.
Use
- HV star winding of the generator step-up transformer (solidly earthed side).
- Star winding of station/auxiliary transformers.
- Small generators with resistance earthing.
For a delta winding, REF is applied using an earthing transformer or the three phase CTs alone (balanced earth fault protection).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Unit generator-transformer schemes · Power Plant Design, chapter 4 · asked 3×
- Restricted earth fault for generator · Switchgear and Protection, chapter 7
- Combined phase and earth fault protection of generator · Switchgear and Protection, chapter 7
- Earth fault protection: 20 MVA alternator · Switchgear and Protection, chapter 7
- Earth fault neutralizer reactance · Switchgear and Protection, chapter 5