Earth fault neutralizer reactance
Short answer
Reactance X_L = 1/(3ωC). For full 1.5 μF, X_L = 707.4 Ω. For 90% length (1.35 μF), X_L = 786.0 Ω. Reactance increases as capacitance decreases to maintain current balance during earth faults.
In a 50 Hz overhead line, the capacitance of one line to earth was 1.5 μF. It was decided to use an earth fault neutralizer. Calculate the reactance to neutralize the capacitance of (i) 100% of length of the line (ii) 90% of length of line.
An earth fault neutraliser (Peterson coil) is a reactor connected between the neutral and earth. During a line-to-earth fault its inductive current equals the capacitive current 3V_phωC of the healthy phases, so:
V_ph / X_L = 3 V_ph ω C → X_L = 1 / (3 ω C)
For a fraction k of the line, C is replaced by kC.
Data
- C = 1.5 μF (line to earth, per phase), f = 50 Hz, ω = 314.16 rad/s
(i) 100% of the line
X_L = 1 / (3 × 314.16 × 1.5×10⁻⁶)
= 1 / 1.4137×10⁻³
= 707.4 Ω
(L = X_L/ω = 2.252 H)
(ii) 90% of the line
C' = 0.9 × 1.5 = 1.35 μF
X_L = 1 / (3 × 314.16 × 1.35×10⁻⁶)
= 1 / 1.2723×10⁻³
= 786.0 Ω
(L = 2.502 H)
Answer: Reactance of the neutraliser = 707.4 Ω for 100% of the line and 786.0 Ω for 90% of the line.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Peterson coil for full and 90% length · Switchgear and Protection, chapter 5
- Arc suppression coil for 66 kV 90 km line · Switchgear and Protection, chapter 5 · asked 6×
- Earth fault protection: 20 MVA alternator · Switchgear and Protection, chapter 7
- Restricted earth fault for generator · Switchgear and Protection, chapter 7
- Combined phase and earth fault protection of generator · Switchgear and Protection, chapter 7
- Arc suppression coil for 0.0125 μF line · Switchgear and Protection, chapter 5
- Effect of earth on line capacitance · Power System Analysis I, chapter 4 · asked 2×
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×