Effect of earth on line capacitance
Short answer
Earth acts as a conducting plane, increasing line capacitance slightly by introducing image charges. The method of images places opposite-charge images below ground, reducing the effective distance between conductors and their images, which raises capacitance. The effect is usually small for overhead lines but important for zero-sequence calculations.
What is the effect of earth on the capacitance of an overhead line? Explain.
The earth is a conductor at zero potential. Its presence changes the electric field of an overhead line and so increases the line capacitance slightly.
Method of images
The earth's surface is an equipotential plane. Its effect can be modelled by removing the earth and placing an image conductor as far below the ground surface as the real conductor is above it, carrying an equal and opposite charge. For a conductor at height h with charge +q, the image is at depth h with charge −q. The field above ground is then calculated from the real and image charges together.
a (+qa) <-- D --> b (+qb)
| |
h h
====|======= earth =====|======
h h
| |
a' (-qa) b' (-qb)
distance a to b' = H = sqrt(D^2 + 4h^2)
Single-phase line
Without earth:
With earth effect (images included):
Because , the denominator is smaller and the capacitance is larger.
Three-phase transposed line
Here is the distance from conductor i to the image of conductor j, and is the distance to its own image.
Points to note
- The earth brings charge of the opposite sign closer to the conductor, which raises the capacitance.
- The effect is small for normal overhead lines, because , so it is usually neglected. It becomes important for low-height lines, large spacings, and in unbalanced-fault (zero-sequence) calculations.
- Earth has a negligible effect on line inductance under balanced conditions.
- Higher capacitance means slightly more charging current and charging kVAR.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Effect of neglecting earth on capacitance · Power System Analysis I, chapter 4
- Capacitance with and without earth effect · Power System Analysis I, chapter 4
- Single-phase line capacitance, 6 mm, 1.3 m · Power System Analysis I, chapter 4
- Transposition; single-phase capacitance with earth · Power System Analysis I, chapter 4
- Proximity effect in overhead lines · Power System Analysis I, chapter 4
- Proximity effect in cables vs overhead lines · Power System Analysis I, chapter 4
- Voltage rise at cable–overhead line junction · High Voltage Engineering, chapter 3 · asked 2×
- Surge from overhead line into cable and transformer · High Voltage Engineering, chapter 3
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×