- 2068 Bhadra · 6 marks
Effect of neglecting earth on capacitance
Short answer
Without earth capacitance = 8.940 nF/km, with earth = 9.012 nF/km; neglecting earth gives about 0.8% lower capacitance, a small error when height (13 m) is large relative to spacing.
For a 3-phase overhead line as shown in the figure below, show the effect of neglecting the presence of earth surface in computing the capacitance of the line. Assume solid, round conductors for each phase. [Figure: conductors a, b, c in a horizontal row 13 m above ground; Dab = Dbc = 6 m, Dca = 12 m; ra = rb = rc = 15 mm.]
The earth is included by the method of images. For a transposed line,
Without the earth, the second term is dropped.
a o-----6 m-----o b-----6 m-----o c
|13 m |13 m |13 m
========================================= earth
|13 m |13 m |13 m
a'o o b' o c'
Data: m, m, m, m.
Neglecting earth
Considering earth
| Distance | Value (m) |
|---|---|
| 26 | |
| 26.683 | |
| 28.636 |
Effect of neglecting earth
Neglecting the earth gives a capacitance about 0.8% lower than the true value. The earth slightly increases the capacitance because the opposite-sign image charges lower the potential of each conductor, so more charge is needed for the same voltage. The error is small when the height (13 m) is large compared with the spacing, so the earth effect is usually neglected.
Answer: without earth nF/km; with earth nF/km; error from neglecting earth ≈ 0.8%.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Capacitance with and without earth effect · Power System Analysis I, chapter 4
- Single-phase line capacitance, 6 mm, 1.3 m · Power System Analysis I, chapter 4
- Effect of earth on line capacitance · Power System Analysis I, chapter 4 · asked 2×
- Transposition; single-phase capacitance with earth · Power System Analysis I, chapter 4
- Inductance of unsymmetrical transposed line · Power System Analysis I, chapter 4
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- Below and above grade water proofing · Building Technology, chapter 1
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- Solid and suspended ground floor · Building Technology, chapter 7 · asked 2×