- 2068 Bhadra · 5 marks
Inductance of unsymmetrical transposed line
Short answer
Deq = 5.7044 m, r' = 0.7788×5 = 3.894 mm. Per-phase inductance L = 2×10⁻⁷ ln(Deq/r') = 1.458 mH/km.
A 3-phase, 50 Hz, overhead line has three phase conductors with the following configuration. Compute the inductance per phase per km if each of the phase conductors is round solid of 10 mm diameter. Assume completely transposed line. [Figure: conductors a, b, c at the corners of a triangle with Dab = 4.5 m, Dbc = 5.5 m, Dca = 7.5 m.]
For a completely transposed line with unsymmetrical spacing, the inductance per phase is H/m, where .
a
/ \
4.5 m/ \7.5 m
/ \
b-------c
5.5 m
Data: diameter 10 mm, mm m, m.
Equivalent spacing
Inductance per phase
Answer: mH per phase per km.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Transposition and inductance of transposed line · Power System Analysis I, chapter 4 · asked 2×
- Inductance of twin-bundle line, 16 mm radius · Power System Analysis I, chapter 4 · asked 3×
- Inductance of composite-conductor single-phase line · Power System Analysis I, chapter 4
- 330 kV quad-bundle line: inductance and charging · Power System Analysis I, chapter 4
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- Inductance of 420 kV line, transposed and untransposed · High Voltage Engineering, chapter 5
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3
- Minimum spacing for 30 mm conductors (m = 0.95) · High Voltage Engineering, chapter 5 · asked 4×
- Inductance matrix of 500 kV bundled line · High Voltage Engineering, chapter 5 · asked 3×