- Asked 3/20
- 2073 Magh · 8 marks
Inductance matrix of 500 kV bundled line
Short answer
Self-inductance 1.158 mH/km, adjacent mutual 0.209 mH/km, outer-outer mutual 0.102 mH/km. Matrix: [[1.158, 0.209, 0.102], [0.209, 1.158, 0.209], [0.102, 0.209, 1.158]] mH/km.
A 500 kV, three phase transmission line has flat horizontal configuration with two sub-conductors per bundle. The inter-phase spacing of the line is 15 m. The radius of each sub-conductor in a bundle is 5 cm and the separation between sub-conductors in a bundle is 30 cm. Calculate the inductance matrix if the average ground clearance of the line is 20 m.
For an EHV line, the inductance matrix is mH/km. is Maxwell's coefficient matrix from the image method, using the equivalent radius of each bundle (internal flux linkage neglected).
Data
- 500 kV, flat horizontal, m, m
- , sub-conductor radius cm, bundle spacing cm
- H/m mH/km
1 2 3
o--- 15 m--o--- 15 m--o
| H = 20 m
////////////////////////////////
Step 1: Equivalent radius
Step 2: Maxwell coefficients ( m)
Step 3: Inductance matrix (untransposed)
Step 4: If transposed (for comparison)
Positive-sequence reactance at 50 Hz: /km.
| Element | Value (mH/km) |
|---|---|
| Self, | 1.1577 |
| Mutual, adjacent (, ) | 0.2093 |
| Mutual, outer–outer () | 0.1022 |
Answer: mH/km.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Capacitance and charge matrices (9.81 m clearance) · High Voltage Engineering, chapter 5 · asked 3×
- Capacitance matrices, untransposed and transposed (15 m) · High Voltage Engineering, chapter 5 · asked 3×
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- Charge matrix of 400 kV line · High Voltage Engineering, chapter 5
- Audible noise of 750 kV line (20 kV/cm gradient) · High Voltage Engineering, chapter 5 · asked 3×
- RI of 330 kV line at point M · High Voltage Engineering, chapter 5
- Check corona on 765 kV line · High Voltage Engineering, chapter 5
- Inductance of 420 kV line, transposed and untransposed · High Voltage Engineering, chapter 5
- Inductance of 3-conductor bundled line, 6.1 m spacing · Power System Analysis I, chapter 4
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Inductance of twin-bundle line, 16 mm radius · Power System Analysis I, chapter 4 · asked 3×