Audible noise of 750 kV line (20 kV/cm gradient)
Short answer
With sub-conductor diameter 30 cm as printed, distances from the microphone are 28.28, 40.31, and 53.85 m. Applying the AN formula gives phase levels 105.42, 103.66, and 102.23 dB(A); power addition gives 108.7 dB(A). If the intended diameter was 3 cm, the total is 53.7 dB(A).
A 750 kV flat horizontally configured transmission line has average ground clearance of 20 m and phase spacing of 15 m. The line uses bundle conductor of 2 × 0.30 diameter in meter. Determine the audible noise (AN) at ground level at horizontal distance of 20 m from the outer most conductor. Assume electric field gradient at the surface of the conductor 20 kV/cm. Use empirical formula for AN due to ith conductor as: AN(i) = 120 log10 Em(i) + 55 log10 d − 11.4 log10 N − 115.4. Here, Em is in kV/cm, D in m and d in cm.
The audible noise from each phase is calculated with the empirical formula using its own distance to the microphone. The three contributions are then added on an energy basis.
Data and reading of the question
- Flat horizontal line, m, phase spacing m
- Bundle of sub-conductors, diameter given as 0.30 m, so cm
- All phases: kV/cm
- Microphone at ground level, 20 m horizontally beyond the outermost phase
- The "" term in the formula is read as , since the note gives units for (in m) and the distance must enter:
P1 P2 P3
o--15 m---o--15 m---o H=20 m
///////////////////////////////[mic]
|<- 20 m ->|
Step 1: Distances to the microphone
Horizontal distances are 20, 35 and 50 m.
Step 2: Common part
Step 3: AN from each phase
Step 4: Total AN
| Phase | (m) | AN (dB(A)) |
|---|---|---|
| Nearest outer | 28.28 | 105.42 |
| Centre | 40.31 | 103.66 |
| Far outer | 53.85 | 102.23 |
| Total | 108.74 |
Note on the conductor size
A 30 cm sub-conductor is unrealistically large; the intended value is probably 0.030 m (3 cm). With cm the term becomes 26.24 instead of 81.24, so every level drops by exactly 55 dB. The phase levels become 50.42, 48.66 and 47.23 dB(A), and the total is 53.74 dB(A), a typical value for a 750 kV line.
Answer: AN ≈ 108.7 dB(A) with cm as printed (≈ 53.7 dB(A) if cm is intended).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Audible noise of 750 kV line (formula with Di) · High Voltage Engineering, chapter 5 · asked 3×
- Audible noise of 750 kV line using two formulas · High Voltage Engineering, chapter 5
- Audible noise of 765 kV line (18 kV/cm outer) · High Voltage Engineering, chapter 5 · asked 4×
- Audible noise of 765 kV line (18.4 kV/cm outer) · High Voltage Engineering, chapter 5 · asked 4×
- Audible noise of 735 kV line at 30 m · High Voltage Engineering, chapter 5 · asked 4×
- Total audible noise of 735 kV line · High Voltage Engineering, chapter 5
- Inductance matrix of 500 kV bundled line · High Voltage Engineering, chapter 5 · asked 3×
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- Inductance of 3-conductor bundled line, 6.1 m spacing · Power System Analysis I, chapter 4