Total audible noise of 735 kV line
Short answer
Calculate AN_i = 120 log Emi + 55 log d − 11.4 log Di + 26.4 log N − 128.4 for each phase using distances to measuring point (25.61, 36.06, 48.33 m). AN values: 49.85, 52.50, 46.71 dB(A). Summing energetically: total AN = 55.07 dB(A).
A 735 kV line has the following details N = 4, d = 3.05 cm, bundle spacing = 45.72 cm, height = 20 m, phase separation = 14 m in horizontal configuration. The maximum conductor surface voltage gradients are 20 kV/cm and 18.4 kV/cm for the centre and outer phase respectively. Calculate the total Audible Noise level in dB at a distance 30 m along the ground from the centre phase. (Empirical relation for AN is: AN(i) = 120 log10 Em(i) + 55 log10(d) − 11.4 log10 D(i) + 26.4 log10 N − 128.4)
The AN of each phase is calculated with the empirical relation using the distance from that phase to the measuring point on the ground. The levels are then added on an energy (power) basis.
Data
- , cm, bundle spacing 45.72 cm (not needed in the formula)
- m, m (horizontal)
- = 20 kV/cm (centre) and 18.4 kV/cm (outer phases)
- Measuring point on the ground, 30 m from the centre phase
Step 1: Distances
The outer phases are m and m away horizontally.
Step 2: AN of each phase
Constant part: .
Step 3: Total AN
| Phase | (m) | AN (dB(A)) |
|---|---|---|
| Near outer | 25.61 | 49.85 |
| Centre | 36.06 | 52.50 |
| Far outer | 48.33 | 46.71 |
| Total | 55.07 |
Sound levels in dB cannot be added arithmetically. Two equal sources add only 3 dB, so the total (55.1) is only about 2.6 dB above the loudest phase.
Answer: total AN ≈ 55.1 dB(A).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Audible noise of 735 kV line at 30 m · High Voltage Engineering, chapter 5 · asked 4×
- Audible noise of 765 kV line (18 kV/cm outer) · High Voltage Engineering, chapter 5 · asked 4×
- Audible noise of 765 kV line (18.4 kV/cm outer) · High Voltage Engineering, chapter 5 · asked 4×
- Audible noise of 750 kV line (20 kV/cm gradient) · High Voltage Engineering, chapter 5 · asked 3×
- Audible noise of 750 kV line (formula with Di) · High Voltage Engineering, chapter 5 · asked 3×
- Audible noise of 750 kV line using two formulas · High Voltage Engineering, chapter 5
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Inductance of 3-conductor bundled line, 6.1 m spacing · Power System Analysis I, chapter 4