Inductance of 3-conductor bundled line, 6.1 m spacing

Short answer

For a three-subconductor bundle per phase, the self GMD of the bundle is Ds^b = ∛(r' d²) = 0.09726 m, with r' = 0.009891 m and d = 0.305 m. The mutual GMD for the horizontal transposed line is Dm = ∛(6.1×6.1×12.2) = 7.686 m. Inductance L = 2×10⁻⁷ ln(Dm/Ds^b) = 0.874 mH/km per phase.

A 3-phase single circuit bundled conductor line with three sub conductors per phase has a horizontal configuration with spacing of 6.1 m between the center lines of adjacent phases as shown in figure. The distance between the sub conductors of each phase is 30.5 cm and each sub conductor has a diameter of 2.54 cm. Find the inductance per phase per km. [Figure: three phases side by side in a horizontal row, each a triangular bundle of three sub-conductors 30.5 cm apart; phase centres 6.1 m apart, outer phases 12.2 m apart.]

For a bundled, transposed line the inductance per phase is

L=2×10−7ln⁡DmDsb H/mL = 2\times10^{-7}\ln\frac{D_m}{D_s^b}\ \text{H/m}

Here DsbD_s^b is the self-GMD (GMR) of the bundle and DmD_m is the mutual GMD between phases. The bundle spacing (0.305 m) is much smaller than the phase spacing, so distances between phases are taken centre to centre. The line is assumed to be fully transposed.

Data

  • Sub-conductor radius: r=2.54/2=1.27r = 2.54/2 = 1.27 cm =0.0127= 0.0127 m
  • GMR of a solid sub-conductor: r′=0.7788r=0.7788×0.0127=0.009891r' = 0.7788r = 0.7788\times0.0127 = 0.009891 m
  • Sub-conductor spacing: d=0.305d = 0.305 m (equilateral triangle)

Self-GMD of the three-conductor bundle

Dsb=(r′ d d)39=r′d23=0.009891×0.30523=0.09726 m\begin{aligned} D_s^b &= \sqrt[9]{(r'\,d\,d)^3} = \sqrt[3]{r'd^2}\\ &= \sqrt[3]{0.009891\times0.305^2}\\ &= 0.09726\ \text{m} \end{aligned}

Mutual GMD

Horizontal arrangement: Dab=Dbc=6.1D_{ab} = D_{bc} = 6.1 m and Dca=12.2D_{ca} = 12.2 m.

Dm=6.1×6.1×12.23=6.1×23=7.686 mD_m = \sqrt[3]{6.1\times6.1\times12.2} = 6.1\times\sqrt[3]{2} = 7.686\ \text{m}

Inductance

L=2×10−7ln⁡7.6860.09726 H/m=2×10−7×ln⁡(79.02)=2×10−7×4.3697=0.8739×10−6 H/m=0.8739 mH/km\begin{aligned} L &= 2\times10^{-7}\ln\frac{7.686}{0.09726}\ \text{H/m}\\ &= 2\times10^{-7}\times\ln(79.02) = 2\times10^{-7}\times4.3697\\ &= 0.8739\times10^{-6}\ \text{H/m} = 0.8739\ \text{mH/km} \end{aligned}

If the frequency is 50 Hz, the reactance is XL=2π×50×0.8739×10−3=0.2746 ΩX_L = 2\pi\times50\times0.8739\times10^{-3} = 0.2746\ \Omega/km per phase.

QuantityValue
r′r'0.009891 m
DsbD_s^b0.09726 m
DmD_m7.686 m
L0.8739 mH/km per phase

Answer: L≈0.874L \approx 0.874 mH per phase per km (XL≈0.275 ΩX_L \approx 0.275\ \Omega/km at 50 Hz).