400 kV line with 3-conductor bundles: reactances and VAR
Short answer
Compute bundle self GMDs: D_sL = (r' d²)^(1/3) = 0.1356 m, D_sC = (r d²)^(1/3) = 0.1474 m, D_m = 12.599 m. Then X_L = 0.2847 Ω/km, X_C = 2.545×10^5 Ω·km, I_c = 0.907 A/km, Q_c = 209.5 kVAR/km per phase.
Determine the inductive and capacitive reactance, charging current and charging VAR per phase per km of the 400 kV single circuit, 3-φ 50 Hz fully transposed transmission line having three bundle conductors per phase with spacing of sub conductors as d = 40 cm and radius of each sub conductor is 20 mm as shown in figure below. [Figure: horizontal single-circuit line; each phase is a triangular bundle of three sub-conductors with 40 cm sides; centres of adjacent phases 10 m apart.]
Each phase is a 3-conductor bundle at the corners of an equilateral triangle of side . We find the bundle self-GMD for inductance and capacitance, the mutual GMD between phases, and then the reactances.
o o o
o o o o o o
A 10 m B 10 m C
d = 40 cm, r = 20 mm
Data: m, m, m, m, 400 kV, 50 Hz.
GMDs
Inductive reactance per km
Capacitive reactance per km
Charging current and VAR per phase per km
(Three phases together: 628.6 kVAR/km.)
Answer: /km, -km, A/km, kVAR/km per phase.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- Capacitive reactance and charging of 2-conductor bundle line · Power System Analysis I, chapter 4 · asked 2×
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4
- Charging VAR of 132 kV equilateral line · Power System Analysis I, chapter 4
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- Inductive reactance of vertical 132 kV line · Power System Analysis I, chapter 4
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- Charging current of 132 kV line, 6 m equilateral · Power System Analysis I, chapter 4
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4