- Asked 2/23
- 2073 Magh · 8 marks
400 kV twin-bundle line: reactances and charging VAR
Short answer
With D_sL = √(r′d) = 0.07893 m, D_sC = √(rd) = 0.08944 m, mutual GMD = 12.599 m, the per km per phase inductive reactance is 0.3187 Ω/km, capacitive reactance 2.831×10⁵ Ω·km, and charging reactive power 188.4 kVAR/km.
Determine the inductive and capacitive reactance and charging VAR per phase per km of a 400 kV single circuit, 3-φ, 50 Hz transposed transmission line having two bundle conductors per phase with spacing of sub conductors as d = 40 cm and radius of each sub-conductor is 20 mm. [Figure: horizontal single-circuit line, phases A, B, C each a two-conductor bundle (a–a', b–b', c–c') with 40 cm between sub-conductors; 10 m between centres of adjacent phases.]
Each phase is a two-conductor bundle. The self-GMD of a 2-bundle is for inductance and for capacitance.
o--o o--o o--o
a a' b b' c c'
A 10 m B 10 m C
d = 40 cm, r = 20 mm
Data: m, m, m, m, 400 kV, 50 Hz.
GMDs
Inductive reactance per phase per km
Capacitive reactance per phase per km
Charging VAR per phase per km
Answer: /km, -km, charging kVAR per phase per km (565.2 kVAR/km for all three phases).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×
- Capacitive reactance and charging of 2-conductor bundle line · Power System Analysis I, chapter 4 · asked 2×
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4
- 330 kV quad-bundle line: inductance and charging · Power System Analysis I, chapter 4
- Charging VAR of 132 kV equilateral line · Power System Analysis I, chapter 4
- Inductive reactance of vertical 132 kV line · Power System Analysis I, chapter 4
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- T/F: double earth wire for 400 kV single circuit · Transmission and Distribution System Design, chapter 3
- Inductance of 420 kV line, transposed and untransposed · High Voltage Engineering, chapter 5
- Tower dimensions for 220 kV single circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×