Inductive reactance of vertical 132 kV line
Short answer
Inductive reactance per phase is 49.1 Ω for 120 km (0.409 Ω/km).
A 120 km long 50 Hz, 132 kV, 3-phase overhead line has flat vertical configuration and uses conductors with radii 12 mm. The spacing between adjacent phases is 5 m. Assuming complete transposition, compute the inductive reactance per phase for the line.
For a transposed line, per phase and .
a o --
5 m
b o -- D_ab = D_bc = 5 m
5 m D_ca = 10 m
c o --
Data: m, m, 50 Hz, 120 km.
Equivalent spacing
Inductance
Inductive reactance
Answer: per phase for 120 km (0.409 Ω/km).