132 kV horizontal line: susceptance and charging

Short answer

Assuming conductor radius 12 mm and transposition, Deq = 5.67 m. Capacitance = 9.03 nF/km, giving shunt susceptance 2.84 µS/km per phase (341 µS for 120 km), charging current 0.216 A/km, and total reactive power 5.93 MVAR.

A 120 km long, 50 Hz, 3 phase, 132 kV overhead line has flat horizontal configuration with distance between adjacent phases equal to 4.5 m and distance between extreme end phases equalling 9 m. Compute the shunt capacitive susceptance per phase, charging current per phase per km and the reactive power generated by the line.

The conductor radius is not given; it is assumed to be 12 mm (a common value for 132 kV lines in IOE problems). For a transposed line, Cn=2πε0/ln⁡(Deq/r)C_n = 2\pi\varepsilon_0/\ln(D_{eq}/r) and the shunt susceptance is B=ωCB = \omega C.

   a o----4.5 m----o b----4.5 m----o c
     |<----------- 9 m ----------->|

Data: Dab=Dbc=4.5D_{ab} = D_{bc} = 4.5 m, Dca=9D_{ca} = 9 m, r=0.012r = 0.012 m, 132 kV, 50 Hz, 120 km.

Equivalent spacing

Deq=4.5×4.5×93=5.6696 mD_{eq} = \sqrt[3]{4.5 \times 4.5 \times 9} = 5.6696\ \text{m}

Capacitance per phase

C=2πε0ln⁡(Deq/r)=55.63×10−12ln⁡(5.6696/0.012)=55.63×10−126.1580=9.034×10−12 F/m=9.034 nF/km\begin{aligned} C &= \frac{2\pi\varepsilon_0}{\ln(D_{eq}/r)} = \frac{55.63\times10^{-12}}{\ln(5.6696/0.012)} = \frac{55.63\times10^{-12}}{6.1580} \\ &= 9.034\times10^{-12}\ \text{F/m} = 9.034\ \text{nF/km} \end{aligned}

Shunt susceptance per phase

B=ωC=2π×50×9.034×10−9=2.838×10−6 S/kmB120=2.838×10−6×120=3.406×10−4 S\begin{aligned} B &= \omega C = 2\pi \times 50 \times 9.034\times10^{-9} = 2.838\times10^{-6}\ \text{S/km} \\ B_{120} &= 2.838\times10^{-6} \times 120 = 3.406\times10^{-4}\ \text{S} \end{aligned}

Charging current per phase per km

Ic=VpB=132 0003×2.838×10−6=76 210×2.838×10−6=0.2163 A/kmI_c = V_p B = \frac{132\,000}{\sqrt3} \times 2.838\times10^{-6} = 76\,210 \times 2.838\times10^{-6} = 0.2163\ \text{A/km}

Reactive power generated by the line (120 km, 3 phase)

Q=VL2B120=(132×103)2×3.406×10−4=5.934 MVARQ = V_L^2 B_{120} = (132\times10^3)^2 \times 3.406\times10^{-4} = 5.934\ \text{MVAR}

Answer (with r=12r = 12 mm): B=2.838 μB = 2.838\ \muS/km per phase (340.6 µS for 120 km), Ic=0.216I_c = 0.216 A/km, Q=5.93Q = 5.93 MVAR.