- 2072 Magh · 10 marks
330 kV quad-bundle line: inductance and charging
Short answer
Assuming sub-conductor radius 12 mm, with D_sL = 0.18629 m, D_sC = 0.19830 m, mutual GMD = 7.5595 m, per phase per km: inductance 0.7407 mH/km, charging current 0.915 A/km, total three-phase charging reactive power 0.523 MVAR/km.
A 3 phase overhead line has 4 sub-conductors per phase separated from each other by 45 cm and placed at the vertices of a square. The phases have flat horizontal configuration with centre to centre distance between adjacent phases equalling 6 m and between far end phases equalling 12 m. Assuming complete transposition determine the inductance per phase, charging current per phase per km and total charging VAR of the line. The line is operated at 330 kV and 50 Hz.
Each phase is a square bundle of four sub-conductors with side m. The sub-conductor radius is not given; it is assumed to be 12 mm (the usual value in this IOE problem).
o o o o o o
o o o o o o
A 6 m B 6 m C
|<------- 12 m ------->|
Data: m, m, m, 330 kV, 50 Hz.
GMDs
Inductance per phase
Charging current per phase per km
Total charging VAR
The line length is not given, so the total is per km; for a line of length km, MVAR (e.g. 104.6 MVAR for 200 km).
Answer: mH/km per phase, A/km per phase, MVAR/km (all three phases), with mm assumed.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- 132 kV horizontal line: susceptance and charging · Power System Analysis I, chapter 4
- Charging current of 60 Hz horizontal 132 kV line · Power System Analysis I, chapter 4
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4
- RI of 330 kV line at point M · High Voltage Engineering, chapter 5
- Inductance matrix of 500 kV bundled line · High Voltage Engineering, chapter 5 · asked 3×
- Audible noise of 765 kV line (18 kV/cm outer) · High Voltage Engineering, chapter 5 · asked 4×
- Audible noise of 765 kV line (18.4 kV/cm outer) · High Voltage Engineering, chapter 5 · asked 4×