- 2073 Bhadra · 10 marks
400 kV quadruple bundle line, 20 m spacing
Short answer
Using bundle self GMD D_sL = 0.22907 m, D_sC = 0.24384 m and mutual GMD = 25.198 m, per phase per km: inductive reactance X_L = 0.2953 Ω/km, capacitive reactance X_C = 2.654×10⁵ Ω·km, charging current I_c = 0.870 A/km, charging reactive power Q_c = 201.0 kVAR/km.
Figure below shows a quadruple-conductor circuit of a single-circuit, three-phase, 400 kV, 50 Hz line with a horizontal spacing of 20 m. Each sub-conductor of the bundle has a diameter of 40 mm and spacing between the sub-conductors is 0.5 m. Each phase group shares the total current and charge equally and the line is completely transposed. Determine the inductive reactance, capacitive reactance, charging current and charging VAR per phase per km of the line. [Figure: horizontal single-circuit line; each phase A, B, C is a square bundle of four sub-conductors with 0.5 m sides; centres of adjacent phases 20 m apart.]
Each phase is a square bundle of four sub-conductors. We find the bundle self-GMD for inductance and capacitance, the mutual GMD, and then the per-km quantities.
o o o o o o
o o o o o o
A 20 m B 20 m C
d = 0.5 m, diameter 40 mm
Data: mm m, m, m, m, 400 kV, 50 Hz.
GMDs
Inductive reactance per phase per km
Capacitive reactance per phase per km
Charging current and VAR
Answer: /km, -km, A/km, kVAR/km per phase (603 kVAR/km for three phases).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Capacitive reactance and charging of 2-conductor bundle line · Power System Analysis I, chapter 4 · asked 2×
- Inductance of 3-conductor bundled line, 6.1 m spacing · Power System Analysis I, chapter 4
- RI levels of 400 kV line at 1 MHz · High Voltage Engineering, chapter 5
- Charge matrix of 400 kV line · High Voltage Engineering, chapter 5
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- Minimum spacing for 30 mm conductors (m = 0.95) · High Voltage Engineering, chapter 5 · asked 4×