Capacitive reactance and charging of 2-conductor bundle line

Short answer

Bundle self-GMD = sqrt(0.009*0.40)=0.06 m; mutual GMD = (10*10*20)^(1/3)=12.599 m. Capacitance C = 2*pi*epsilon0 / ln(12.599/0.06) = 0.0104 µF/km. At 50 Hz, Xc = 1/(ωC) = 3.06e5 Ω·km. Assuming 400 kV line, charging current = 0.755 A/km, reactive power per phase = 174 kVAR/km (523 kVAR/km three-phase).

Calculate the capacitive reactance, charging current and charging VAR per phase per km of a three-phase transmission line with bundle conductor as shown in figure below. Given that radius of each conductor is 9 mm and the line is transposed. [Figure: horizontal single-circuit line, phases A, B, C each a two-conductor bundle (a–a', b–b', c–c') with 40 cm between sub-conductors; 10 m between centres of adjacent phases.]

The voltage and frequency are not printed. They are assumed as 400 kV (line), 50 Hz, the usual data for this two-conductor-bundle configuration. Reactance per km does not depend on the voltage; only the charging current and VAR scale with it.

Data

  • Sub-conductor radius r=9r = 9 mm =0.009= 0.009 m. Bundle spacing d=0.40d = 0.40 m.
  • Phase spacing: 10 m, 10 m, 20 m (horizontal), transposed.
  • Vph=400/3=230.94V_{ph} = 400/\sqrt3 = 230.94 kV; ω=314.16\omega = 314.16 rad/s.

Self-GMD for capacitance

For capacitance the actual radius r is used, not r′r':

Dsc=r d=0.009×0.40=0.06 mD_{sc} = \sqrt{r\,d} = \sqrt{0.009\times0.40} = 0.06\ \text{m}

Mutual GMD

Deq=10×10×203=12.599 mD_{eq} = \sqrt[3]{10\times10\times20} = 12.599\ \text{m}

Capacitance and capacitive reactance per phase per km

C=2πε0ln⁡(Deq/Dsc)=5.563×10−11ln⁡(12.599/0.06)=5.563×10−115.3470=1.0404×10−11 F/m=0.010404 μF/kmXC=1ωC=1314.16×1.0404×10−8=3.059×105 Ω⋅km\begin{aligned} C &= \frac{2\pi\varepsilon_0}{\ln(D_{eq}/D_{sc})} = \frac{5.563\times10^{-11}}{\ln(12.599/0.06)} = \frac{5.563\times10^{-11}}{5.3470}\\ &= 1.0404\times10^{-11}\ \text{F/m} = 0.010404\ \mu\text{F/km}\\ X_C &= \frac{1}{\omega C} = \frac{1}{314.16\times1.0404\times10^{-8}} = 3.059\times10^5\ \Omega\cdot\text{km} \end{aligned}

Charging current and charging VAR (per km)

Ic=VphXC=2309403.059×105=0.7548 A/kmQc,ph=VphIc=230940×0.7548=174.32 kVAR/km per phaseQc,3ϕ=3×174.32=522.97 kVAR/km\begin{aligned} I_c &= \frac{V_{ph}}{X_C} = \frac{230940}{3.059\times10^5} = 0.7548\ \text{A/km}\\ Q_{c,ph} &= V_{ph}I_c = 230940\times0.7548 = 174.32\ \text{kVAR/km per phase}\\ Q_{c,3\phi} &= 3\times174.32 = 522.97\ \text{kVAR/km} \end{aligned}
Quantity (per phase per km)Value
DscD_{sc}0.06 m
DeqD_{eq}12.599 m
C0.010404 μF
XCX_C0.3059 MΩ·km
IcI_c (400 kV assumed)0.755 A
Charging VAR174.3 kVAR (523.0 kVAR for 3 phases)

Answer: XC≈3.06×105 ΩX_C \approx 3.06\times10^5\ \Omega·km per phase. At 400 kV, Ic≈0.755I_c \approx 0.755 A/km and the charging VAR is about 174.3 kVAR per phase per km. (At another line voltage V, scale IcI_c by V/400V/400 and the VAR by (V/400)2(V/400)^2.)

✓ Answer checked by Claude Opus 5.5 (high effort)

All Power System Analysis I chapter 4 questions →