- Asked 2/23
- 2079 Chaitra · 8 marks
Capacitive reactance and charging of 2-conductor bundle line
Short answer
Bundle self-GMD = sqrt(0.009*0.40)=0.06 m; mutual GMD = (10*10*20)^(1/3)=12.599 m. Capacitance C = 2*pi*epsilon0 / ln(12.599/0.06) = 0.0104 µF/km. At 50 Hz, Xc = 1/(ωC) = 3.06e5 Ω·km. Assuming 400 kV line, charging current = 0.755 A/km, reactive power per phase = 174 kVAR/km (523 kVAR/km three-phase).
Calculate the capacitive reactance, charging current and charging VAR per phase per km of a three-phase transmission line with bundle conductor as shown in figure below. Given that radius of each conductor is 9 mm and the line is transposed. [Figure: horizontal single-circuit line, phases A, B, C each a two-conductor bundle (a–a', b–b', c–c') with 40 cm between sub-conductors; 10 m between centres of adjacent phases.]
The voltage and frequency are not printed. They are assumed as 400 kV (line), 50 Hz, the usual data for this two-conductor-bundle configuration. Reactance per km does not depend on the voltage; only the charging current and VAR scale with it.
Data
- Sub-conductor radius mm m. Bundle spacing m.
- Phase spacing: 10 m, 10 m, 20 m (horizontal), transposed.
- kV; rad/s.
Self-GMD for capacitance
For capacitance the actual radius r is used, not :
Mutual GMD
Capacitance and capacitive reactance per phase per km
Charging current and charging VAR (per km)
| Quantity (per phase per km) | Value |
|---|---|
| 0.06 m | |
| 12.599 m | |
| C | 0.010404 μF |
| 0.3059 MΩ·km | |
| (400 kV assumed) | 0.755 A |
| Charging VAR | 174.3 kVAR (523.0 kVAR for 3 phases) |
Answer: ·km per phase. At 400 kV, A/km and the charging VAR is about 174.3 kVAR per phase per km. (At another line voltage V, scale by and the VAR by .)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- Capacitance of double circuit line, 6 mm radius · Power System Analysis I, chapter 4
- Inductance of twin-bundle line, 16 mm radius · Power System Analysis I, chapter 4 · asked 3×
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3
- Capacitance matrices, untransposed and transposed (15 m) · High Voltage Engineering, chapter 5 · asked 3×
- Capacitance and charge matrices, transposed and untransposed · High Voltage Engineering, chapter 5
- Single-phase Cu cable for three loads · Industrial Power Distribution and Illumination, chapter 5