- 2082 Shrawan · 8 marks
Capacitance and charge matrices, transposed and untransposed
Short answer
Average height 9.858 m, bundle equiv. radius 12.04 cm. Untransposed C (pF/m): diag 11.12, 11.30, 11.12; off-diag -1.47, -0.42. Charges 2.79, 2.95, 2.79 μC/m rms. Transposed: C_s=11.14, C_m=-1.10 pF/m, C1=12.24 nF/km, charge 2.83 μC/m rms per phase.
A 400 kV three phase transmission line has flat horizontal configuration with two sub-conductors per bundle and a phase spacing of 11.3 m. The height of the phase conductors is 11.875 m and 8.85 m at tower and at midspan respectively. The radius of each sub-conductor in the bundle is 3.17 cm and the separation between the sub-conductors is 45.72 cm. Calculate the capacitance and charge matrices of this line for both untransposed and transposed configurations.
The capacitance matrix is found from Maxwell's coefficients, using the average height over the span and the equivalent bundle radius. The charge matrix then follows from .
Data
- 400 kV, flat horizontal, m,
- Sub-conductor radius cm (as given); bundle spacing cm
- Height at tower 11.875 m, at midspan 8.85 m
- pF/m
Step 1: Average height (parabolic sag)
Step 2: Equivalent radius
Step 3: Maxwell coefficients
Untransposed line
Charge matrix. Take balanced phase voltages kV rms (). Then :
Peak values are 3.95, 4.17 and 3.95 μC/m. The centre phase carries the most charge, so it has the highest surface gradient.
Transposed line
Average the coefficients:
The positive-sequence capacitance is
and each phase charge is equal in magnitude:
Answer: untransposed , , , pF/m, with charges 2.79/2.95/2.79 μC/m rms; transposed , pF/m, nF/km, with μC/m rms per phase.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Capacitance matrices, untransposed and transposed (15 m) · High Voltage Engineering, chapter 5 · asked 3×
- Capacitance and charge matrices (9.81 m clearance) · High Voltage Engineering, chapter 5 · asked 3×
- Charge matrix of 400 kV line · High Voltage Engineering, chapter 5
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- Inductance of 420 kV line, transposed and untransposed · High Voltage Engineering, chapter 5
- RI of 400 kV line at 0.5 MHz · High Voltage Engineering, chapter 5
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×