Short answer

Compute Maxwell's coefficient matrix using average height (9.858 m) and equivalent bundle radius (8.513 cm). The capacitance matrix has diagonal values 10.39 and 10.53 pF/m. The RMS charge matrix gives outer phases 2.60 μC/m, centre 2.73 μC/m (peak 3.67, 3.86, 3.67 μC/m).

A 400 kV three phase transmission line has flat horizontal configuration with 2 × 3.17 cm diameter bundle in each phase and a phase spacing of 11.3 m. The heights of the phase conductors are 11.875 m and 8.85 m at tower and at midspan respectively. The separation between the sub-conductors is 45.72 cm. Calculate the charge matrix of this line.

The charge matrix is [Q]=[C][V]=2πε0[M]−1[V][Q] = [C][V] = 2\pi\varepsilon_0 [M]^{-1}[V]. Here [M][M] is Maxwell's coefficient matrix, built from the average height of the sagging conductor and the equivalent bundle radius.

Data

  • 400 kV, flat horizontal, S=11.3S = 11.3 m
  • Bundle 2×3.172 \times 3.17 cm diameter, so r=1.585r = 1.585 cm; B=45.72B = 45.72 cm
  • Heights 11.875 m (tower) and 8.85 m (midspan)
  • 2πε0=55.562\pi\varepsilon_0 = 55.56 pF/m

Step 1: Average height

Hav=8.85+11.875−8.853=9.858 m,2H=19.717 mH_{av} = 8.85 + \frac{11.875 - 8.85}{3} = 9.858\ \text{m}, \quad 2H = 19.717\ \text{m}

Step 2: Equivalent radius

req=rB=1.585×45.72=8.513 cmr_{eq} = \sqrt{rB} = \sqrt{1.585 \times 45.72} = 8.513\ \text{cm}

Step 3: Maxwell coefficient matrix

Mii=ln⁡19.7170.08513=5.4451M12=M23=ln⁡11.32+19.717211.3=0.6987M13=ln⁡22.62+19.717222.6=0.2830\begin{aligned} M_{ii} &= \ln\frac{19.717}{0.08513} = 5.4451 \\ M_{12} = M_{23} &= \ln\frac{\sqrt{11.3^2 + 19.717^2}}{11.3} = 0.6987 \\ M_{13} &= \ln\frac{\sqrt{22.6^2 + 19.717^2}}{22.6} = 0.2830 \end{aligned} [M]=[5.44510.69870.28300.69875.44510.69870.28300.69875.4451],det⁡=155.96[M] = \begin{bmatrix} 5.4451 & 0.6987 & 0.2830 \\ 0.6987 & 5.4451 & 0.6987 \\ 0.2830 & 0.6987 & 5.4451 \end{bmatrix}, \quad \det = 155.96

Step 4: Capacitance (charge-coefficient) matrix

[M]−1=[0.18697−0.02312−0.00675−0.023120.18959−0.02312−0.00675−0.023120.18697][M]^{-1} = \begin{bmatrix} 0.18697 & -0.02312 & -0.00675 \\ -0.02312 & 0.18959 & -0.02312 \\ -0.00675 & -0.02312 & 0.18697 \end{bmatrix} [C]=55.56 [M]−1=[10.387−1.285−0.375−1.28510.533−1.285−0.375−1.28510.387] pF/m[C] = 55.56\,[M]^{-1} = \begin{bmatrix} 10.387 & -1.285 & -0.375 \\ -1.285 & 10.533 & -1.285 \\ -0.375 & -1.285 & 10.387 \end{bmatrix}\ \text{pF/m}

Step 5: Charge matrix

Balanced phase voltages: V=400/3=230.94V = 400/\sqrt{3} = 230.94 kV rms at 0°,−120°,+120°0°, -120°, +120°.

q1=230.94 (10.387−1.285∠−120°−0.375∠120°)×10−3=2.597∠4.02° μC/m\begin{aligned} q_1 &= 230.94\,(10.387 - 1.285\angle{-120°} - 0.375\angle{120°}) \times 10^{-3} \\ &= 2.597\angle 4.02°\ \mu\text{C/m} \end{aligned}

Similarly:

[Q]=[2.597∠4.02°2.729∠−120°2.597∠115.98°] μC/m (rms)[Q] = \begin{bmatrix} 2.597\angle 4.02° \\ 2.729\angle -120° \\ 2.597\angle 115.98° \end{bmatrix}\ \mu\text{C/m (rms)}

Peak values: 3.67, 3.86 and 3.67 μC/m.

PhaseCharge (rms)Charge (peak)
Outer 12.597 μC/m3.67 μC/m
Centre2.729 μC/m3.86 μC/m
Outer 32.597 μC/m3.67 μC/m

The centre phase carries about 5% more charge than the outer phases, so its conductor surface gradient is the highest.

Answer: [C][C] as above (diagonal 10.39/10.53 pF/m); charges ≈ 2.60, 2.73, 2.60 μC/m rms (3.67, 3.86, 3.67 μC/m peak).