- 2080 Chaitra · 8 marks
Charge matrix of 400 kV line
Short answer
Compute Maxwell's coefficient matrix using average height (9.858 m) and equivalent bundle radius (8.513 cm). The capacitance matrix has diagonal values 10.39 and 10.53 pF/m. The RMS charge matrix gives outer phases 2.60 μC/m, centre 2.73 μC/m (peak 3.67, 3.86, 3.67 μC/m).
A 400 kV three phase transmission line has flat horizontal configuration with 2 × 3.17 cm diameter bundle in each phase and a phase spacing of 11.3 m. The heights of the phase conductors are 11.875 m and 8.85 m at tower and at midspan respectively. The separation between the sub-conductors is 45.72 cm. Calculate the charge matrix of this line.
The charge matrix is . Here is Maxwell's coefficient matrix, built from the average height of the sagging conductor and the equivalent bundle radius.
Data
- 400 kV, flat horizontal, m
- Bundle cm diameter, so cm; cm
- Heights 11.875 m (tower) and 8.85 m (midspan)
- pF/m
Step 1: Average height
Step 2: Equivalent radius
Step 3: Maxwell coefficient matrix
Step 4: Capacitance (charge-coefficient) matrix
Step 5: Charge matrix
Balanced phase voltages: kV rms at .
Similarly:
Peak values: 3.67, 3.86 and 3.67 μC/m.
| Phase | Charge (rms) | Charge (peak) |
|---|---|---|
| Outer 1 | 2.597 μC/m | 3.67 μC/m |
| Centre | 2.729 μC/m | 3.86 μC/m |
| Outer 3 | 2.597 μC/m | 3.67 μC/m |
The centre phase carries about 5% more charge than the outer phases, so its conductor surface gradient is the highest.
Answer: as above (diagonal 10.39/10.53 pF/m); charges ≈ 2.60, 2.73, 2.60 μC/m rms (3.67, 3.86, 3.67 μC/m peak).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Capacitance and charge matrices, transposed and untransposed · High Voltage Engineering, chapter 5
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- Inductance matrix of 500 kV bundled line · High Voltage Engineering, chapter 5 · asked 3×
- RI levels of 400 kV line at 1 MHz · High Voltage Engineering, chapter 5
- RI of 400 kV line at 0.5 MHz · High Voltage Engineering, chapter 5
- Capacitance and charge matrices (9.81 m clearance) · High Voltage Engineering, chapter 5 · asked 3×
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×
- 330 kV quad-bundle line: inductance and charging · Power System Analysis I, chapter 4