Capacitance matrices, untransposed and transposed (15 m)

Short answer

Untransposed: self 10.50/10.81 pF/m, adjacent mutual -1.91 pF/m, outer mutual -0.63 pF/m. Transposed: self 10.54 pF/m, mutual -1.46 pF/m; positive-sequence capacitance 12.0 nF/km.

A 400 kV, three phase transmission line has flat horizontal configuration with two sub-conductors per bundle. The average ground clearance is 15 m and the inter phase spacing is 11 m. The radius of each sub-conductor in the bundle is 3.18 cm and the separation between the sub-conductors is 45.72 cm. Calculate the capacitance matrices for both the untransposed and the transposed conditions.

The capacitance matrix is [C]=2πε0[M]−1[C] = 2\pi\varepsilon_0[M]^{-1} with Maxwell's coefficients from the image method. For the transposed line, the self and mutual coefficients are averaged before inversion.

Data

  • 400 kV, flat horizontal, S=11S = 11 m, H=15H = 15 m
  • r=3.18r = 3.18 cm, B=45.72B = 45.72 cm, N=2N = 2
  • 2πε0=1/(18×109)=55.562\pi\varepsilon_0 = 1/(18 \times 10^9) = 55.56 pF/m

Step 1: Equivalent radius

req=rB=3.18×45.72=12.058 cmr_{eq} = \sqrt{rB} = \sqrt{3.18 \times 45.72} = 12.058\ \text{cm}

Step 2: Maxwell coefficients

Mii=ln⁡300.12058=5.5167M12=M23=ln⁡112+30211=1.0664M13=ln⁡222+30222=0.5253\begin{aligned} M_{ii} &= \ln\frac{30}{0.12058} = 5.5167 \\ M_{12} = M_{23} &= \ln\frac{\sqrt{11^2 + 30^2}}{11} = 1.0664 \\ M_{13} &= \ln\frac{\sqrt{22^2 + 30^2}}{22} = 0.5253 \end{aligned}

Untransposed condition

[M]=[5.51671.06640.52531.06645.51671.06640.52531.06645.5167],det⁡=155.02[M] = \begin{bmatrix} 5.5167 & 1.0664 & 0.5253 \\ 1.0664 & 5.5167 & 1.0664 \\ 0.5253 & 1.0664 & 5.5167 \end{bmatrix}, \quad \det = 155.02 [M]−1=[0.18899−0.03434−0.01136−0.034340.19454−0.03434−0.01136−0.034340.18899][M]^{-1} = \begin{bmatrix} 0.18899 & -0.03434 & -0.01136 \\ -0.03434 & 0.19454 & -0.03434 \\ -0.01136 & -0.03434 & 0.18899 \end{bmatrix} [C]=55.56 [M]−1=[10.499−1.908−0.631−1.90810.808−1.908−0.631−1.90810.499] pF/m[C] = 55.56\,[M]^{-1} = \begin{bmatrix} 10.499 & -1.908 & -0.631 \\ -1.908 & 10.808 & -1.908 \\ -0.631 & -1.908 & 10.499 \end{bmatrix}\ \text{pF/m}

Transposed condition

Average the coefficients:

Ms=5.5167Mm=1.0664+1.0664+0.52533=0.8860\begin{aligned} M_s &= 5.5167 \\ M_m &= \frac{1.0664 + 1.0664 + 0.5253}{3} = 0.8860 \end{aligned} [Mt]=[5.51670.88600.88600.88605.51670.88600.88600.88605.5167][M_t] = \begin{bmatrix} 5.5167 & 0.8860 & 0.8860 \\ 0.8860 & 5.5167 & 0.8860 \\ 0.8860 & 0.8860 & 5.5167 \end{bmatrix}

For a matrix with equal off-diagonal terms, the inverse has

Cs=2πε0Ms+Mm(Ms−Mm)(Ms+2Mm),Cm=−2πε0Mm(Ms−Mm)(Ms+2Mm)C_s = 2\pi\varepsilon_0\frac{M_s + M_m}{(M_s - M_m)(M_s + 2M_m)}, \quad C_m = -2\pi\varepsilon_0\frac{M_m}{(M_s - M_m)(M_s + 2M_m)} [Ct]=[10.539−1.458−1.458−1.45810.539−1.458−1.458−1.45810.539] pF/m[C_t] = \begin{bmatrix} 10.539 & -1.458 & -1.458 \\ -1.458 & 10.539 & -1.458 \\ -1.458 & -1.458 & 10.539 \end{bmatrix}\ \text{pF/m}

Sequence capacitances:

C1=Cs−Cm=55.56Ms−Mm=55.564.6307=12.00 nF/kmC0=Cs+2Cm=55.56Ms+2Mm=55.567.2887=7.62 nF/km\begin{aligned} C_1 &= C_s - C_m = \frac{55.56}{M_s - M_m} = \frac{55.56}{4.6307} = 12.00\ \text{nF/km} \\ C_0 &= C_s + 2C_m = \frac{55.56}{M_s + 2M_m} = \frac{55.56}{7.2887} = 7.62\ \text{nF/km} \end{aligned}
ElementUntransposed (pF/m)Transposed (pF/m)
C11C_{11}, C33C_{33}10.49910.539
C22C_{22}10.80810.539
C12C_{12}, C23C_{23}−1.908−1.458
C13C_{13}−0.631−1.458

Transposition makes all phases identical and gives a balanced positive-sequence capacitance of 12.0 nF/km.

Answer: untransposed [C][C] diagonal 10.50/10.81, off-diagonal −1.91/−0.63 pF/m; transposed Cs=10.54C_s = 10.54, Cm=−1.46C_m = -1.46 pF/m, C1=12.0C_1 = 12.0 nF/km.