Capacitance matrices, untransposed and transposed (15 m)
Short answer
Untransposed: self 10.50/10.81 pF/m, adjacent mutual -1.91 pF/m, outer mutual -0.63 pF/m. Transposed: self 10.54 pF/m, mutual -1.46 pF/m; positive-sequence capacitance 12.0 nF/km.
A 400 kV, three phase transmission line has flat horizontal configuration with two sub-conductors per bundle. The average ground clearance is 15 m and the inter phase spacing is 11 m. The radius of each sub-conductor in the bundle is 3.18 cm and the separation between the sub-conductors is 45.72 cm. Calculate the capacitance matrices for both the untransposed and the transposed conditions.
The capacitance matrix is with Maxwell's coefficients from the image method. For the transposed line, the self and mutual coefficients are averaged before inversion.
Data
- 400 kV, flat horizontal, m, m
- cm, cm,
- pF/m
Step 1: Equivalent radius
Step 2: Maxwell coefficients
Untransposed condition
Transposed condition
Average the coefficients:
For a matrix with equal off-diagonal terms, the inverse has
Sequence capacitances:
| Element | Untransposed (pF/m) | Transposed (pF/m) |
|---|---|---|
| , | 10.499 | 10.539 |
| 10.808 | 10.539 | |
| , | −1.908 | −1.458 |
| −0.631 | −1.458 |
Transposition makes all phases identical and gives a balanced positive-sequence capacitance of 12.0 nF/km.
Answer: untransposed diagonal 10.50/10.81, off-diagonal −1.91/−0.63 pF/m; transposed , pF/m, nF/km.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Capacitance and charge matrices (9.81 m clearance) · High Voltage Engineering, chapter 5 · asked 3×
- Inductance matrix of 500 kV bundled line · High Voltage Engineering, chapter 5 · asked 3×
- Capacitance and charge matrices, transposed and untransposed · High Voltage Engineering, chapter 5
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- Inductance of 420 kV line, transposed and untransposed · High Voltage Engineering, chapter 5
- Charge matrix of 400 kV line · High Voltage Engineering, chapter 5
- RI levels of 400 kV line at 1 MHz · High Voltage Engineering, chapter 5
- Audible noise of 750 kV line using two formulas · High Voltage Engineering, chapter 5
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- 400 kV quadruple bundle line, 20 m spacing · Power System Analysis I, chapter 4
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×