- Asked 3/23
- 2070 Magh · 5 marks
Inductance of twin-bundle line, 16 mm radius
Short answer
Inductance per phase is 0.968 mH/km, giving 145.1 mH for 150 km.
Compute the inductance per phase for a 150 km line using phase conductors of 16 mm radius and configured as given below. Assume complete transposition of the phases. [Figure: horizontal single-circuit line; each phase a, b, c is a two-conductor bundle with sub-conductor spacing d = 45 cm; centres of adjacent phases D = 7.5 m apart.]
Each phase is a two-conductor bundle, so its self-GMD for inductance is . The line is transposed, so .
o--o o--o o--o
a 7.5 m b 7.5 m c
d = 45 cm, r = 16 mm
Data: m, m, m, m, 150 km.
Mutual GMD
Self GMD of bundle
Inductance
Answer: mH per phase for 150 km (0.968 mH/km).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- L and C of triple-bundle line, D=8 m · Power System Analysis I, chapter 4 · asked 2×
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Inductance of composite-conductor single-phase line · Power System Analysis I, chapter 4
- 400 kV twin-bundle line: reactances and charging VAR · Power System Analysis I, chapter 4 · asked 2×
- Capacitive reactance and charging of 2-conductor bundle line · Power System Analysis I, chapter 4 · asked 2×
- 330 kV quad-bundle line: inductance and charging · Power System Analysis I, chapter 4
- Inductance of 3-conductor bundled line, 6.1 m spacing · Power System Analysis I, chapter 4
- Inductance matrix of 500 kV bundled line · High Voltage Engineering, chapter 5 · asked 3×
- Most economical span, 180 km single circuit · Transmission and Distribution System Design, chapter 4
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4