Most economical span, 180 km single circuit

Calculate most economical span for 180 km long single circuit transmission system with single earth wire chosen, considering the following design step data.

Span (m)Dmax (m)H1 (m)H2 (m)H3 (m)Ht (m)
2503.1510.2213.6016.9828.84
3004.3211.4014.7218.0429.98
3505.4812.5815.9519.3231.22

Where H1: height of lower conductor from ground, H2: height of middle conductor from ground, H3: height of top conductor from ground, Ht: total height of tower. The power conductor has maximum working tension of 6860 kg and diameter of 25.2 mm. The earth wire has maximum working tension of 2840 kg and diameter of 16.4 mm. Assume the towers consisted to be 80% type A, and other remaining are of type B in the system and the wind force of 100 kg/m².

Method. For each span, the transverse load at the tower comes from two sources:

  • wind on the conductors and earth wires: F=p×d×SF = p \times d \times S, taking the wind span equal to the span SS and using the full projected area;
  • the resultant of the conductor tensions at a line deviation θ\theta: Fd=2Tsin⁡(θ/2)F_d = 2T\sin(\theta/2).

These loads act at the conductor heights. Their overturning moment at ground level is

M=nc (Fc+Fdc)(h1+h2+h3)+ne (Fe+Fde) HtM = n_c\,(F_c + F_{dc})(h_1 + h_2 + h_3) + n_e\,(F_e + F_{de})\,H_t

where ncn_c is the number of conductors at each level and nen_e the number of earth wires. The tower weight is found from Ryle's formula

W=K HtMW = K\,H_t\sqrt{M}

KK is the same for all spans, so it cancels in the comparison. Tower cost is proportional to tower weight, so the span that gives the smallest total tower weight is the most economical span (with the conductor already fixed). Wind on the tower body is neglected.

Assumptions

  • Single circuit: one conductor at each of H1H_1, H2H_2, H3H_3 (nc=1n_c = 1), and one earth wire at HtH_t (ne=1n_e = 1).
  • Standard tower types (IS 802 practice): type A is a suspension tower for 0°–2° deviation and type B is a small-angle tower for 2°–15°. Each type is designed for its maximum angle.
  • Number of towers for 180 km: N=⌈180000/S⌉+1N = \lceil 180000/S \rceil + 1, with 80% type A and 20% type B.

Deviation loads

TypeFdc=2×6860sin⁡(θ/2)F_{dc} = 2 \times 6860 \sin(\theta/2)Fde=2×2840sin⁡(θ/2)F_{de} = 2 \times 2840 \sin(\theta/2)
A (2°)239.45 kg99.13 kg
B (15°)1,790.82 kg741.39 kg

Wind loads (p=100p = 100 kg/m²)

Span (m)Fc=p dc SF_c = p\,d_c\,S (kg)Fe=p de SF_e = p\,d_e\,S (kg)
250630.00410.00
300756.00492.00
350882.00574.00

Moments and tower weight index

Sample calculation (250 m, type A):

Mc=(630+239.45)(10.22+13.60+16.98)=35,473.4 kg⋅mMe=(410+99.13)(28.84)=14,683.3 kg⋅mHtM=28.8450156.7=6,458.9\begin{aligned} M_c &= (630 + 239.45)(10.22 + 13.60 + 16.98) = 35{,}473.4\ \text{kg·m} \\ M_e &= (410 + 99.13)(28.84) = 14{,}683.3\ \text{kg·m} \\ H_t\sqrt{M} &= 28.84\sqrt{50156.7} = 6{,}458.9 \end{aligned}
Span (m)Tower type (θ)McM_c (kg·m)MeM_e (kg·m)MM (kg·m)HtMH_t\sqrt{M}
250A (2°)35,473.414,683.350,156.76,458.9
250B (15°)98,769.433,206.1131,975.510,477.1
300A (2°)43,958.917,722.161,681.07,445.7
300B (15°)112,467.536,977.0149,444.511,589.7
350A (2°)53,661.221,015.174,676.38,531.5
350B (15°)127,894.441,066.4168,960.812,832.9

Total tower steel for the line

Weighted index =0.8(HtM)A+0.2(HtM)B= 0.8(H_t\sqrt{M})_A + 0.2(H_t\sqrt{M})_B, multiplied by the number of towers NN:

Span (m)Weighted HtMH_t\sqrt{M}Towers NNRelative tower steel N×HtMN\times H_t\sqrt{M}
2507,262.67215.236 × 10⁶
3008,274.56014.973 × 10⁶
3509,391.85164.846 × 10⁶

The total tower weight keeps falling up to the largest span tabulated.

Answer: the most economical span is 350 m (lowest total tower weight index, 4.846 × 10⁶ K, with 516 towers).