Skip to main content

Economical span, 200 km, 10% angle towers

Short answer

Using conductor working tension 4000 kg (UTS 8000 kg, safety factor 2) and wind 80 kg/m², overturning moments are computed for straight and 15° angle towers. A weighted index (90% straight, 10% angle) gives total tower steel over 200 km; minimum occurs at 350 m with 3.870×10⁶ relative steel.

To transmit the given amount of power to a given distance a single circuit with single earth wire is chosen for which the following design steps are completed, compute the most economical span if the transmission length is 200 km. Assume 10% of towers have been used to take care of maximum angle deviation of 15° and rest are straight line towers.

Span (m)Dmax (m)H1 (m)H2 (m)H3 (m)Ht (m)
2503.1410.24513.55516.86528.815
2753.6910.80114.11117.42129.371
3004.2711.38314.69318.00329.953
3254.8811.96515.29818.60830.558
3505.5012.54815.92319.23331.183

Where H1: height of lower conductor from ground, H2: height of middle conductor from ground, H3: height of top conductor from ground, Ht: total height of tower. The power conductor has UTS of 8000 kg and diameter of 20 mm. The earth wire has maximum working tension of 4000 kg and diameter of 16 mm. Wind force: 80 kg/m² and factor of safety for tension is 2.

Method. For each span, the transverse load at the tower comes from two sources:

  • wind on the conductors and earth wires: F=p×d×SF = p \times d \times S, taking the wind span equal to the span SS and using the full projected area;
  • the resultant of the conductor tensions at a line deviation θ\theta: Fd=2Tsin⁡(θ/2)F_d = 2T\sin(\theta/2).

These loads act at the conductor heights. Their overturning moment at ground level is

M=nc (Fc+Fdc)(h1+h2+h3)+ne (Fe+Fde) HtM = n_c\,(F_c + F_{dc})(h_1 + h_2 + h_3) + n_e\,(F_e + F_{de})\,H_t

where ncn_c is the number of conductors at each level and nen_e the number of earth wires. The tower weight is found from Ryle's formula

W=K HtMW = K\,H_t\sqrt{M}

KK is the same for all spans, so it cancels in the comparison. Tower cost is proportional to tower weight, so the span that gives the smallest total tower weight is the most economical span (with the conductor already fixed). Wind on the tower body is neglected.

Data

  • Conductor working tension Tc=UTS/FOS=8000/2=4000T_c = \text{UTS}/\text{FOS} = 8000/2 = 4000 kg, dc=0.020d_c = 0.020 m.
  • Earth wire Te=4000T_e = 4000 kg, de=0.016d_e = 0.016 m. Wind pressure p=80p = 80 kg/m².
  • Single circuit with single earth wire: nc=1n_c = 1, ne=1n_e = 1.
  • 90% straight towers (no deviation load) and 10% angle towers designed for 15°.
  • N=⌈200000/S⌉+1N = \lceil 200000/S \rceil + 1.

Deviation load on the angle towers:

Fdc=Fde=2×4000×sin⁡7.5°=1,044.21 kgF_{dc} = F_{de} = 2 \times 4000 \times \sin 7.5° = 1,044.21\ \text{kg}

Wind loads

Span (m)Fc=p dc SF_c = p\,d_c\,S (kg)Fe=p de SF_e = p\,d_e\,S (kg)
250400.00320.00
275440.00352.00
300480.00384.00
325520.00416.00
350560.00448.00

Moments and tower weight index

Sample calculation (250 m, angle tower):

Mc=(400+1044.21)(10.245+13.555+16.865)=58,728.8 kg⋅mMe=(320+1044.21)(28.815)=39,309.7 kg⋅mHtM=28.81598038.5=9,022.3\begin{aligned} M_c &= (400 + 1044.21)(10.245 + 13.555 + 16.865) = 58{,}728.8\ \text{kg·m} \\ M_e &= (320 + 1044.21)(28.815) = 39{,}309.7\ \text{kg·m} \\ H_t\sqrt{M} &= 28.815\sqrt{98038.5} = 9{,}022.3 \end{aligned}
Span (m)Tower type (θ)McM_c (kg·m)MeM_e (kg·m)MM (kg·m)HtMH_t\sqrt{M}
250straight (0°)16,266.09,220.825,486.84,600.2
250angle (15°)58,728.839,309.798,038.59,022.3
275straight (0°)18,626.510,338.628,965.14,998.7
275angle (15°)62,831.041,008.1103,839.19,464.5
300straight (0°)21,157.911,502.032,659.95,413.1
300angle (15°)67,185.642,779.2109,964.89,932.7
325straight (0°)23,852.912,712.136,565.05,843.3
325angle (15°)71,751.944,621.1116,372.910,424.4
350straight (0°)26,714.213,970.040,684.26,289.7
350angle (15°)76,527.246,531.6123,058.810,938.9

Total tower steel for 200 km

Weighted index =0.9 (straight)+0.1 (angle)= 0.9\,(\text{straight}) + 0.1\,(\text{angle}):

Span (m)Weighted HtMH_t\sqrt{M}Towers NNRelative tower steel N×HtMN\times H_t\sqrt{M}
2505,042.48014.039 × 10⁶
2755,445.37293.970 × 10⁶
3005,865.16683.918 × 10⁶
3256,301.46173.888 × 10⁶
3506,754.65733.870 × 10⁶

Answer: the most economical span is 350 m (573 towers: about 516 straight and 57 angle towers). The curve is flat beyond 300 m, so 325–350 m spans are nearly equally economical.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Transmission and Distribution System Design chapter 4 questions →