Initial line design for 200 MW over 120 km

Short answer

Economical voltage ~217 kV, select standard 220 kV single circuit. Insulator string requires 15 discs, length 2.31 m. Cross-arm length is 4.27 m, vertical conductor separation 4.94 m, horizontal separation 8.53 m, and earth wire height above top conductor 7.39 m.

For a transmission line to deliver a power of 200 MW over a distance of 120 km carryout the following line design initial steps: a. Find the most economical voltage, check the design capability curve and hence suggest the standard voltage and no. of circuit. b. Determine the no of insulator discs. c. Find the following air clearances with justifications: i. Cross arm length ii. Insulator string length iii. Horizontal and vertical separation of conductor iv. Height of earth wire from the top most conductor.

[Given: Most economical voltage empirical formula: V = 5.5 × [Lt/1.6 + (P × 1000)/(cosφ × Nc × 150)]^0.5 kV, with Lt in km and P in MW. Standard voltages: 66 kV, 132 kV, 220 kV, 400 kV.]

[Given Table A-1: Transmission line capability curve with assumption of single circuit transmission line surge impedance of 400 Ω (m.f. = power transmission capability/SIL):]

Length (km)Multiplying factor
802.75
1602.25
2401.75
3201.35
4801.0
6400.75

[Given Table A-2: Withstand voltage capability for different system voltages:]

Maximum system voltage (kV)1 minute dry withstand (kV)1 minute wet withstand (kV)Impulse withstand (kV)
123215185450
145265230550
255435395900
4207606801550

[Given Table A-3: Flashover voltages for 254 × 154 mm disc insulators:]

No. of discs1 minute dry FOV (kV)1 minute wet FOV (kV)Impulse FOV (kV)
18050150
215590255
3215130355
4270170440
5325210525
6380250610
7435290695
8485330780
9535370860
10585410945
116354501025
126854851105
137305201185
147755551265
158205901345
168656201425
179106501505
189556801585
1910007101665
2010457401745

[Other given data: Minimum air clearance: 6.5 inch per 10 kV (rms) and factor of safety = 8 inch. Maximum insulator string swing: 45°. Toughest condition: 0°C, 100 kg/m² wind, no ice. Easiest condition: 60°C, no wind. Stringing condition: 27°C, no wind. Minimum ground clearance: (V − 33)/33 + 17 ft, where V is L-L maximum system voltage.]

Given: P=200P = 200 MW, L=120L = 120 km. Assumed cos⁡ϕ=0.9\cos\phi = 0.9, Zc=400 ΩZ_c = 400\ \Omega, factors FWR = 1.15, NACF = 1.1, FOS = 1.1 (usual design values), disc spacing 154 mm. Maximum system voltage of the 220 kV class = 255 kV (Table A-2).

a. Economical voltage, capability, standard voltage and circuits

V=5.5L1.6+1000Pcos⁡ϕ Nc×150V = 5.5\sqrt{\frac{L}{1.6} + \frac{1000P}{\cos\phi\,N_c \times 150}}

Nc=1N_c = 1: V=5.575+1481.48=5.5×39.452=216.99V = 5.5\sqrt{75 + 1481.48} = 5.5 \times 39.452 = 216.99 kV Nc=2N_c = 2: V=5.575+740.74=5.5×28.561=157.09V = 5.5\sqrt{75 + 740.74} = 5.5 \times 28.561 = 157.09 kV

m.f. at 120 km =2.75−4080(0.5)=2.50= 2.75 - \frac{40}{80}(0.5) = 2.50.

OptionSIL (MW)Capability (MW)Remark
132 kV D/C43.56217.80Only 8.9% margin; 108.9 MW on N-1
220 kV S/C121302.50Adequate, 51% margin
220 kV D/C121605.00Over-design

VeconV_{econ} for S/C (217 kV) almost equals 220 kV. Selected: 220 kV, single circuit (vertical/triangular formation, one earth wire).

b. Number of insulator discs

k=1.15×1.1×1.1=1.3915k = 1.15 \times 1.1 \times 1.1 = 1.3915

Over-voltageRequired FOVDiscs from Table A-3
Lightning: 900×k900 \times k1252.35 kV (impulse)14 (1265 kV)
Power freq. wet: 395×k395 \times k549.64 kV14 (555 kV)
Power freq. dry: 435×k435 \times k605.30 kV11 (635 kV)
Switching, SSR = 2.8573.62 kV rms equiv.15 (590 kV wet)

Switching: Vss=2.8×2×255/3=582.98V_{ss} = 2.8 \times \sqrt{2} \times 255/\sqrt{3} = 582.98 kV peak; ×k=811.21\times k = 811.21 kV peak =573.62= 573.62 kV rms. This exceeds the 14-disc wet FOV (555 kV), so 15 discs are needed.

Number of discs = 15 per suspension string (switching surge governs).

c. Air clearances

Minimum air clearance (6.5 in per 10 kV of maximum phase rms voltage + 8 in):

Vph=2553=147.22 kVa=6.5×147.2210+8=103.70 in=2.63 m\begin{aligned} V_{ph} &= \frac{255}{\sqrt{3}} = 147.22\ \text{kV} \\ a &= 6.5 \times \frac{147.22}{10} + 8 = 103.70\ \text{in} = 2.63\ \text{m} \end{aligned}

ii. Insulator string length (15 discs × 154 mm, fittings neglected):

l=15×0.154=2.31 ml = 15 \times 0.154 = 2.31\ \text{m}

i. Cross-arm length. With a 45° string swing, the conductor moves lsin⁡45°l\sin45° toward the tower and must still be aa away from the tower body:

CA=lsin⁡45°+a=2.31×0.7071+2.634=1.633+2.634=4.27 mCA = l\sin45° + a = 2.31 \times 0.7071 + 2.634 = 1.633 + 2.634 = 4.27\ \text{m}

iii. Separation of conductors

  • Vertical separation between cross-arms: the conductor hangs ll below its cross-arm and must be aa above the cross-arm below:
dv=l+a=2.31+2.634=4.94 md_v = l + a = 2.31 + 2.634 = 4.94\ \text{m}
  • Horizontal separation between conductors on opposite sides of the tower (tower body width neglected):
dh=2×CA=2×4.267=8.53 md_h = 2 \times CA = 2 \times 4.267 = 8.53\ \text{m}

iv. Height of earth wire above the top conductor. With a single earth wire on the tower axis and a shielding angle of 30°:

h=CAtan⁡30°=4.267×1.732=7.39 mh = \frac{CA}{\tan30°} = 4.267 \times 1.732 = 7.39\ \text{m}
          o  earth wire
          |\
          | \ 30 deg
     7.39 m  \
          |   \
   -------+----o  top phase
   4.27 m |    | string 2.31 m
          |
   4.94 m |
   o------+------o  lower phases
     8.53 m apart
          |
       tower

(Also: minimum ground clearance =(255−33)/33+17=23.73= (255-33)/33 + 17 = 23.73 ft =7.23= 7.23 m.)

(If the IEC value Vmax=245V_{max} = 245 kV were used instead, the switching requirement would be 551.12 kV rms, 14 discs would just suffice, and the clearances would be slightly smaller: a=2.54a = 2.54 m, l=2.16l = 2.16 m, CA=4.06CA = 4.06 m.)

Summary: 220 kV S/C; 15 discs; string length 2.31 m; cross-arm 4.27 m; vertical spacing 4.94 m; horizontal spacing 8.53 m; earth wire 7.39 m above the top conductor.