- 2067 Mangsir (old course) · 6+6+8 marks
Initial line design for 200 MW over 120 km
Short answer
Economical voltage ~217 kV, select standard 220 kV single circuit. Insulator string requires 15 discs, length 2.31 m. Cross-arm length is 4.27 m, vertical conductor separation 4.94 m, horizontal separation 8.53 m, and earth wire height above top conductor 7.39 m.
For a transmission line to deliver a power of 200 MW over a distance of 120 km carryout the following line design initial steps: a. Find the most economical voltage, check the design capability curve and hence suggest the standard voltage and no. of circuit. b. Determine the no of insulator discs. c. Find the following air clearances with justifications: i. Cross arm length ii. Insulator string length iii. Horizontal and vertical separation of conductor iv. Height of earth wire from the top most conductor.
[Given: Most economical voltage empirical formula: V = 5.5 × [Lt/1.6 + (P × 1000)/(cosφ × Nc × 150)]^0.5 kV, with Lt in km and P in MW. Standard voltages: 66 kV, 132 kV, 220 kV, 400 kV.]
[Given Table A-1: Transmission line capability curve with assumption of single circuit transmission line surge impedance of 400 Ω (m.f. = power transmission capability/SIL):]
| Length (km) | Multiplying factor |
|---|---|
| 80 | 2.75 |
| 160 | 2.25 |
| 240 | 1.75 |
| 320 | 1.35 |
| 480 | 1.0 |
| 640 | 0.75 |
[Given Table A-2: Withstand voltage capability for different system voltages:]
| Maximum system voltage (kV) | 1 minute dry withstand (kV) | 1 minute wet withstand (kV) | Impulse withstand (kV) |
|---|---|---|---|
| 123 | 215 | 185 | 450 |
| 145 | 265 | 230 | 550 |
| 255 | 435 | 395 | 900 |
| 420 | 760 | 680 | 1550 |
[Given Table A-3: Flashover voltages for 254 × 154 mm disc insulators:]
| No. of discs | 1 minute dry FOV (kV) | 1 minute wet FOV (kV) | Impulse FOV (kV) |
|---|---|---|---|
| 1 | 80 | 50 | 150 |
| 2 | 155 | 90 | 255 |
| 3 | 215 | 130 | 355 |
| 4 | 270 | 170 | 440 |
| 5 | 325 | 210 | 525 |
| 6 | 380 | 250 | 610 |
| 7 | 435 | 290 | 695 |
| 8 | 485 | 330 | 780 |
| 9 | 535 | 370 | 860 |
| 10 | 585 | 410 | 945 |
| 11 | 635 | 450 | 1025 |
| 12 | 685 | 485 | 1105 |
| 13 | 730 | 520 | 1185 |
| 14 | 775 | 555 | 1265 |
| 15 | 820 | 590 | 1345 |
| 16 | 865 | 620 | 1425 |
| 17 | 910 | 650 | 1505 |
| 18 | 955 | 680 | 1585 |
| 19 | 1000 | 710 | 1665 |
| 20 | 1045 | 740 | 1745 |
[Other given data: Minimum air clearance: 6.5 inch per 10 kV (rms) and factor of safety = 8 inch. Maximum insulator string swing: 45°. Toughest condition: 0°C, 100 kg/m² wind, no ice. Easiest condition: 60°C, no wind. Stringing condition: 27°C, no wind. Minimum ground clearance: (V − 33)/33 + 17 ft, where V is L-L maximum system voltage.]
Given: MW, km. Assumed , , factors FWR = 1.15, NACF = 1.1, FOS = 1.1 (usual design values), disc spacing 154 mm. Maximum system voltage of the 220 kV class = 255 kV (Table A-2).
a. Economical voltage, capability, standard voltage and circuits
: kV : kV
m.f. at 120 km .
| Option | SIL (MW) | Capability (MW) | Remark |
|---|---|---|---|
| 132 kV D/C | 43.56 | 217.80 | Only 8.9% margin; 108.9 MW on N-1 |
| 220 kV S/C | 121 | 302.50 | Adequate, 51% margin |
| 220 kV D/C | 121 | 605.00 | Over-design |
for S/C (217 kV) almost equals 220 kV. Selected: 220 kV, single circuit (vertical/triangular formation, one earth wire).
b. Number of insulator discs
| Over-voltage | Required FOV | Discs from Table A-3 |
|---|---|---|
| Lightning: | 1252.35 kV (impulse) | 14 (1265 kV) |
| Power freq. wet: | 549.64 kV | 14 (555 kV) |
| Power freq. dry: | 605.30 kV | 11 (635 kV) |
| Switching, SSR = 2.8 | 573.62 kV rms equiv. | 15 (590 kV wet) |
Switching: kV peak; kV peak kV rms. This exceeds the 14-disc wet FOV (555 kV), so 15 discs are needed.
Number of discs = 15 per suspension string (switching surge governs).
c. Air clearances
Minimum air clearance (6.5 in per 10 kV of maximum phase rms voltage + 8 in):
ii. Insulator string length (15 discs × 154 mm, fittings neglected):
i. Cross-arm length. With a 45° string swing, the conductor moves toward the tower and must still be away from the tower body:
iii. Separation of conductors
- Vertical separation between cross-arms: the conductor hangs below its cross-arm and must be above the cross-arm below:
- Horizontal separation between conductors on opposite sides of the tower (tower body width neglected):
iv. Height of earth wire above the top conductor. With a single earth wire on the tower axis and a shielding angle of 30°:
o earth wire
|\
| \ 30 deg
7.39 m \
| \
-------+----o top phase
4.27 m | | string 2.31 m
|
4.94 m |
o------+------o lower phases
8.53 m apart
|
tower
(Also: minimum ground clearance ft m.)
(If the IEC value kV were used instead, the switching requirement would be 551.12 kV rms, 14 discs would just suffice, and the clearances would be slightly smaller: m, m, m.)
Summary: 220 kV S/C; 15 discs; string length 2.31 m; cross-arm 4.27 m; vertical spacing 4.94 m; horizontal spacing 8.53 m; earth wire 7.39 m above the top conductor.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Voltage, circuits, discs: 200 MW, 160 km · Transmission and Distribution System Design, chapter 2
- Insulator discs per string, 180 MW over 200 km · Transmission and Distribution System Design, chapter 3
- Voltage and circuits for 300 MW over 200 km · Transmission and Distribution System Design, chapter 2
- Voltage and circuits for 190 MW over 240 km · Transmission and Distribution System Design, chapter 2
- Empirical formula; voltage for 150 MW over 100 km · Transmission and Distribution System Design, chapter 2
- Voltage and circuits for 220 MW over 175 km · Transmission and Distribution System Design, chapter 2
- 450 km 400 kV line, 420 MW, 0.95 pf · Power System Analysis I, chapter 5
- Nominal-T 100 km line, 20 MW at 110 kV · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- 70 km, 40 MW line: regulation and zero-regulation pf · Power System Analysis I, chapter 6
All Transmission and Distribution System Design chapter 2 questions →