Empirical formula; voltage for 150 MW over 100 km
Short answer
The formula balances conductor and insulation costs to find a starting voltage; capability must be checked. For 150 MW over 100 km, economical voltages are 188 kV (single) and 137 kV (double). 132 kV double circuit is selected, as it is nearest the economical value, with 229 MW capability and N-1 reliability.
Discuss and explain the appropriateness of empirical formula used for most economical voltage selection based on number of circuit to transmit P MW power over a distance of L km given in Appendix. Hence choose the most suitable standard voltage and number of circuit for 150 MW power over a distance of 100 km.
Appropriateness of the empirical formula
- It is derived from the balance of costs: conductor and loss cost fall with voltage, insulation and tower cost rise with voltage. The square root reflects from minimising .
- Length term ( converted to miles): longer lines need higher voltage to keep drop and loss low.
- Power term : proportional to kVA per circuit; more power per circuit needs higher voltage. Increasing shares the power and lowers the voltage required.
- Merits: quick, needs only , , pf, ; gives a good starting point; matches common practice.
- Limitations: it is an old empirical (Still's type) formula; it ignores actual costs of conductor, energy and land, does not check stability, regulation, corona or thermal limits, and gives non-standard values. So the result must be rounded to a standard voltage and checked with the SIL-based capability curve.
Selection for 150 MW over 100 km
not given, assumed 0.9.
:
:
Capability: m.f. at 100 km .
| Option | SIL (MW) | Capability (MW) | Remark |
|---|---|---|---|
| 132 kV S/C | 43.56 | 114.34 | < 150, reject |
| 132 kV D/C | 43.56 | 228.69 | OK |
| 220 kV S/C | 121 | 317.62 | OK, large surplus |
- 132 kV D/C: economical voltage 136.7 kV is very close to 132 kV; capability 228.7 MW (52% margin); if one circuit trips the other still carries 114 MW (76% of load).
- 220 kV S/C: economical voltage 188.4 kV lies between 132 and 220 kV; capability is more than twice the need and there is no backup circuit.
Answer: 132 kV, double circuit (closest to economical voltage, adequate capability, better reliability).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Voltage and circuits for 190 MW over 240 km · Transmission and Distribution System Design, chapter 2
- Voltage and circuits for 160 MW over 100 km · Transmission and Distribution System Design, chapter 2
- Voltage, circuits, discs: 200 MW, 160 km · Transmission and Distribution System Design, chapter 2
- Initial line design for 200 MW over 120 km · Transmission and Distribution System Design, chapter 2
- Insulator discs per string, 180 MW over 200 km · Transmission and Distribution System Design, chapter 3
- Voltage and circuits for 300 MW over 200 km · Transmission and Distribution System Design, chapter 2
- Empirical flood formula, 100 sq km catchment · Engineering Hydrology, chapter 6
- 150 km line by T-model, 60 MW · Power System Analysis I, chapter 5
- 150 km line, A = 0.96∠1°: regulation, max power · Power System Analysis I, chapter 6
- Nominal-T 100 km line, 20 MW at 110 kV · Power System Analysis I, chapter 5
All Transmission and Distribution System Design chapter 2 questions →