150 km line by T-model, 60 MW

Short answer

Per-phase VR=76.21 kV, IR=291.6 A lagging 0.9. T-model with Z/2=22.5+j42.5 Ω, Y=j4.241e-4 S gives VS=98.69 kV (170.94 kV line). Results: sending power 70.81 MW, line loss 10.81 MW, efficiency 84.73%, regulation 31.87%.

A 150 km long three phase overhead line has a resistance of 45 ohms per phase, inductive reactance of 85 ohms per phase and capacitance (line to neutral) 9.00 nF per km. It supplies a load of 60 MW at a voltage of 132 kV and pf 0.9 lagging. Find (i) sending end active power (ii) efficiency (iii) line losses and (iv) voltage regulation. Use T-model.

Given: R=45 ΩR = 45\ \Omega, X=85 ΩX = 85\ \Omega per phase (totals); C=9C = 9 nF/km × 150 km =1.35 μ= 1.35\ \muF; load 60 MW, 132 kV, 0.9 p.f. lagging. Frequency assumed 50 Hz.

Z=45+j85 Ω,Z2=22.5+j42.5 ΩY=j2π×50×1.35×10−6=j4.241×10−4 SVR=1323=76.21∠0∘ kVIR=60×1063×132×103×0.9=291.6∠−25.84∘=262.43−j127.10 A\begin{aligned} Z &= 45 + j85\ \Omega, \quad \frac{Z}{2} = 22.5 + j42.5\ \Omega \\ Y &= j2\pi\times50\times1.35\times10^{-6} = j4.241\times10^{-4}\ \text{S} \\ V_R &= \frac{132}{\sqrt3} = 76.21\angle 0^\circ\ \text{kV} \\ I_R &= \frac{60\times10^6}{\sqrt3\times132\times10^3\times0.9} = 291.6\angle -25.84^\circ = 262.43 - j127.10\ \text{A} \end{aligned}

Nominal-T working

 IS     Z/2            Z/2     IR
 o-->--[R/2 jX/2]--+--[R/2 jX/2]-->--o
                   |
 VS              [ Y ] Ic   (VC)     VR
                   |
 o-----------------+-----------------o
VC=VR+IRZ2=87,517+j8294=87.91∠5.41∘ kVIC=YVC=−3.52+j37.12=37.28∠95.41∘ AIS=IR+IC=258.91−j89.98=274.1∠−19.17∘ AVS=VC+ISZ2=97,167+j17,273=98.69∠10.08∘ kVVS(L)=3×98.69=170.94 kV\begin{aligned} V_C &= V_R + I_R\frac{Z}{2} = 87{,}517 + j8294 = 87.91\angle 5.41^\circ\ \text{kV} \\ I_C &= YV_C = -3.52 + j37.12 = 37.28\angle 95.41^\circ\ \text{A} \\ I_S &= I_R + I_C = 258.91 - j89.98 = 274.1\angle -19.17^\circ\ \text{A} \\ V_S &= V_C + I_S\frac{Z}{2} = 97{,}167 + j17{,}273 = 98.69\angle 10.08^\circ\ \text{kV} \\ V_{S(L)} &= \sqrt3\times98.69 = 170.94\ \text{kV} \end{aligned}

Sending p.f. =cos⁡(10.08∘+19.17∘)=0.8725= \cos(10.08^\circ + 19.17^\circ) = 0.8725 lagging.

(i) Sending-end active power

PS=3∣VS∣∣IS∣cos⁡ϕS=3×98.69×103×274.1×0.8725=70.81 MWP_S = 3|V_S||I_S|\cos\phi_S = 3\times98.69\times10^3\times274.1\times0.8725 = 70.81\ \text{MW}

(iii) Line losses (series resistance, R/2R/2 in each arm)

Ploss=3(∣IR∣2+∣IS∣2)R2=3(291.62+274.12)(22.5)=10.81 MW\begin{aligned} P_{loss} &= 3\left(|I_R|^2 + |I_S|^2\right)\frac{R}{2} = 3(291.6^2 + 274.1^2)(22.5) \\ &= 10.81\ \text{MW} \end{aligned}

Check: PS−PR=70.81−60=10.81P_S - P_R = 70.81 - 60 = 10.81 MW.

(ii) Efficiency

η=PRPS×100=6070.81×100=84.73 %\eta = \frac{P_R}{P_S}\times100 = \frac{60}{70.81}\times100 = 84.73\ \%

(iv) Voltage regulation

A=1+ZY/2=0.982∠0.56∘A = 1 + ZY/2 = 0.982\angle 0.56^\circ. No-load receiving voltage:

VR(NL)=∣VS∣∣A∣=98.690.982=100.50 kV/phase=174.07 kV (line)%VR=174.07−132132×100=31.87 %\begin{aligned} V_{R(NL)} &= \frac{|V_S|}{|A|} = \frac{98.69}{0.982} = 100.50\ \text{kV/phase} = 174.07\ \text{kV (line)} \\ \%\text{VR} &= \frac{174.07 - 132}{132}\times100 = 31.87\ \% \end{aligned}

Answer: (i) PS=70.81P_S = 70.81 MW, (ii) η=84.73%\eta = 84.73\%, (iii) line loss =10.81= 10.81 MW, (iv) regulation =31.87%= 31.87\% (with VS=170.94V_S = 170.94 kV, IS=274.1I_S = 274.1 A).

The large regulation and loss arise because R=45 ΩR = 45\ \Omega and X=85 ΩX = 85\ \Omega are high for a 132 kV line carrying 60 MW.