Equivalent-T of 300 km long line
Short answer
Per-phase total Z=145.9∠75.71° Ω, Y=j0.1885 S, γl=5.244∠82.86°, Zc=27.82∠-7.14° Ω. ABCD: A=D=0.8433∠-47.0°, B=31.31∠-80.12° Ω, C=0.04046∠-65.83° S. Equivalent-T: Z'/2=18.51∠-58.73° Ω, Y'=0.04046∠-65.83° S. With VS=220 kV, open-circuit receiving voltage VR(L)=260.88 kV.
A 220 kV, three phase transmission line is 300 km long. The line has resistance of 0.12 ohm per phase per km, line inductance of 1.5 mH per phase per km and shunt capacitance of 2 μF per phase per km. Calculate ABCD parameters of the line with long line model in equivalent T-model. If the line is excited by 220 kV from the sending end, calculate the receiving voltage.
Given (per phase, per km): , mH, F, km, Hz (assumed), kV.
Step 1: Line constants
Step 2: and
Step 3: ABCD constants (long line)
Step 4: Equivalent-T circuit
In the equivalent T, each series arm is and the shunt branch is , with and :
IS Z'/2 Z'/2 IR
o-->--[18.51<-58.7]-+-[18.51<-58.7]-->--o
|
VS Y' = 0.04046<-65.8 S VR
|
o-------------------+-------------------o
Step 5: Receiving-end voltage (open circuit, )
The receiving voltage is higher than 220 kV (Ferranti effect).
Answer: , , S; equivalent T: per arm, S; no-load kV.
Note: 2 μF/km is about 200 times the capacitance of a real overhead line (typically about 0.01 μF/km), which is why and the angles are unusual. With F/km the same steps give , , S and kV.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- 220 kV line on 6-6-12 m triangle · Power System Analysis I, chapter 4
- 12 km line at 32.5 kV: regulation and capacitor · Power System Analysis I, chapter 6
- 12 km 33 kV line: losses, zero-regulation capacitor · Power System Analysis I, chapter 6
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- Shunt reactors for 750 kV line ABCD · High Voltage Engineering, chapter 3
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×
- Inductance matrix of 500 kV bundled line · High Voltage Engineering, chapter 5 · asked 3×
- Peterson coil for 33 kV 60 km line · Switchgear and Protection, chapter 5 · asked 6×