- 2069 Bhadra (old course)
Shunt reactors for 750 kV line ABCD
Short answer
At no load, the receiving-end reactor current is VR/(jXL), giving Vs = VR(0.9 + 130/XL). Requiring VR = 1.05 Vs gives 0.9 + 130/XL = 1/1.05, so XL = 130/0.05238 ≈ 2482 Ω per phase. The reactor rating is about 227 MVAr at 750 kV.
A 750 kV, 500 km transmission line has ABCD parameter given by A = 0.9 and B = j130 Ω. Using the reactive shunt compensation scheme of figure, determine the value of XL so that the receiving end voltage at no load could be controlled as VR = 1.05 Vs. [Figure: line represented as an ABCD two-port between sending end Vs and receiving end VR, with a shunt reactor jXL to ground at each end]
The line is a two-port with , . Shunt reactors are connected at both ends.
Relation at no load
At no load the only "load" on the receiving end of the two-port is the receiving-end reactor:
The sending-end reactor is directly across the source. It changes the current drawn from the source but not the relation between and . Hence
Without compensation
That is an 11% Ferranti rise.
Required reactor for
Check: ✓
Three-phase reactor rating at 750 kV:
Vs o----+----[ A=0.9, B=j130 ]----+----o VR
| |
jXL jXL
| |
--------+-------------------------+----- gnd
Answer: 2482 Ω per phase (about 227 MVAr at 750 kV) at the receiving end. The same value is used at the sending end for a symmetrical scheme.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Expression for receiving-end shunt compensation · High Voltage Engineering, chapter 3
- Mid-line reactor for Vr = Vs at no load · High Voltage Engineering, chapter 3
- Receiving-end voltage infinite at 1500 km · High Voltage Engineering, chapter 3
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×
- Audible noise of 750 kV line (20 kV/cm gradient) · High Voltage Engineering, chapter 5 · asked 3×
- Audible noise of 750 kV line (formula with Di) · High Voltage Engineering, chapter 5 · asked 3×
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
- 8 km line receiving 15000 kVA at 33 kV · Power System Analysis I, chapter 6
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×