Shunt reactors for 750 kV line ABCD

Short answer

At no load, the receiving-end reactor current is VR/(jXL), giving Vs = VR(0.9 + 130/XL). Requiring VR = 1.05 Vs gives 0.9 + 130/XL = 1/1.05, so XL = 130/0.05238 ≈ 2482 Ω per phase. The reactor rating is about 227 MVAr at 750 kV.

A 750 kV, 500 km transmission line has ABCD parameter given by A = 0.9 and B = j130 Ω. Using the reactive shunt compensation scheme of figure, determine the value of XL so that the receiving end voltage at no load could be controlled as VR = 1.05 Vs. [Figure: line represented as an ABCD two-port between sending end Vs and receiving end VR, with a shunt reactor jXL to ground at each end]

The line is a two-port with A=0.9A = 0.9, B=j130 ΩB = j130\ \Omega. Shunt reactors jXLjX_L are connected at both ends.

Relation at no load

At no load the only "load" on the receiving end of the two-port is the receiving-end reactor:

IR=VRjXLI_R = \frac{V_R}{jX_L}

The sending-end reactor is directly across the source. It changes the current drawn from the source but not the relation between VsV_s and VRV_R. Hence

Vs=AVR+BIR=0.9VR+j130⋅VRjXLVs=VR(0.9+130XL)\begin{aligned} V_s &= AV_R + BI_R = 0.9V_R + j130\cdot\frac{V_R}{jX_L} \\ V_s &= V_R\left(0.9 + \frac{130}{X_L}\right) \end{aligned}

Without compensation

VRVs=10.9=1.111 pu\frac{V_R}{V_s} = \frac{1}{0.9} = 1.111\ \text{pu}

That is an 11% Ferranti rise.

Required reactor for VR=1.05VsV_R = 1.05V_s

0.9+130XL=11.05=0.95238130XL=0.05238XL=1300.05238=2481.8 Ω\begin{aligned} 0.9 + \frac{130}{X_L} &= \frac{1}{1.05} = 0.95238 \\ \frac{130}{X_L} &= 0.05238 \\ X_L &= \frac{130}{0.05238} = 2481.8\ \Omega \end{aligned}

Check: 1/(0.9+130/2481.8)=1/0.95238=1.051/(0.9 + 130/2481.8) = 1/0.95238 = 1.05 ✓

Three-phase reactor rating at 750 kV:

Q=V2XL=75022481.8=226.6 MVArQ = \frac{V^2}{X_L} = \frac{750^2}{2481.8} = 226.6\ \text{MVAr}
 Vs o----+----[ A=0.9, B=j130 ]----+----o VR
         |                         |
        jXL                       jXL
         |                         |
 --------+-------------------------+----- gnd

Answer: XL≈X_L \approx 2482 Ω per phase (about 227 MVAr at 750 kV) at the receiving end. The same value is used at the sending end for a symmetrical scheme.