- 2071 Bhadra · 8 marks
Receiving-end voltage infinite at 1500 km
Short answer
For a lossless line at no load, VR = Vs/cos(beta l). With wave velocity 3e5 km/s and 50 Hz, beta = 1.047e-3 rad/km; for 1500 km beta l = 90 degrees, cos beta l = 0, so VR becomes infinite. The line is a quarter-wavelength resonant line.
Starting with the mathematical expression given below. Justify that the voltage at the receiving end of a loss less line of 50 Hz operating frequency becomes infinity when the length of line is 1500 km at no-load condition. [Vs; Is] = [A B; C D][VR; IR]
For a lossless line the ABCD constants are
where is the phase constant and is the surge impedance.
No-load condition
At no load , so
Phase constant for an overhead line
For a lossless overhead line the wave velocity is km/s, so
Wavelength: km.
Line of 1500 km
So a 1500 km line is a quarter-wavelength line (). At no load it is in resonance: the line inductance and capacitance resonate at 50 Hz. In theory the receiving-end voltage is infinite, for any finite sending-end voltage.
| Length (km) | ||
|---|---|---|
| 300 | 18° | 1.051 |
| 600 | 36° | 1.236 |
| 1000 | 60° | 2.000 |
| 1500 | 90° | ∞ |
In practice line resistance and corona losses limit the voltage, but it would still be dangerously high. Very long lines are therefore compensated (shunt reactors, series capacitors) or split into sections by intermediate substations.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Expression for receiving-end shunt compensation · High Voltage Engineering, chapter 3
- Mid-line reactor for Vr = Vs at no load · High Voltage Engineering, chapter 3
- Temporary overvoltage at no load and its remedy · High Voltage Engineering, chapter 3
- Infinite line: surge impedance and forward/backward waves · High Voltage Engineering, chapter 3
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3
- Loss and voltage drop, 16 km uniformly varying load · Transmission and Distribution System Design, chapter 7
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Long line sending end voltage derivation · Power System Analysis I, chapter 5