- 2074 Magh · 8 marks
Loss and voltage drop, 16 km uniformly varying load
Short answer
For uniformly increasing load, loss factor is 8/15, drop factor 2/3. With I_s=100 A, l=16 km, R=9.6 Ω, |z|=0.6708 Ω/km: three-phase power loss = 3×(8/15)×100²×9.6 = 153.6 kW; voltage drop per phase = (2/3)×100×0.6708×16 = 715.5 V, line drop 1239 V (11.3% of 11 kV).
Compute the power loss and maximum voltage drop for a 16 km long 11 kV, 3 phase primary distribution line having sending end current of 100 A with uniformly varying load. (Use R = 0.6 Ω/km and X = 0.3 Ω/km)
Assumption: "uniformly varying load" is taken as a uniformly increasing load, i.e. the load density rises linearly from zero at the sending end to a maximum at the far end (Gonen's case). No power factor is given, so the maximum possible drop is found using (the drop is largest when it equals ).
Current distribution
Let load density (A/km). The current at distance from the source is the load beyond :
Voltage drop (per phase)
Power loss (three-phase)
Substitution
A, km, , /km.
Comparison with other load patterns
| Load type | Drop factor | Loss factor |
|---|---|---|
| Lumped at end | 1 | 1 |
| Uniformly distributed | 1/2 | 1/3 |
| Uniformly increasing | 2/3 | 8/15 |
Answer: Power loss = 153.6 kW; maximum voltage drop ≈ 715.5 V per phase = 1239 V line (≈ 11.3 % of 11 kV).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Voltage drop and loss, uniformly varying load · Transmission and Distribution System Design, chapter 7 · asked 2×
- Loss and drop, 15 km 11 kV feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Power loss, 10 km 11 kV UDL feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Voltage drop and loss with uniformly distributed load · Transmission and Distribution System Design, chapter 7 · asked 2×
- LT loss and voltage drop, four 2 km feeders · Transmission and Distribution System Design, chapter 7 · asked 2×
- LT feeder options: loss and voltage drop, 50 kW · Transmission and Distribution System Design, chapter 7 · asked 3×
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Long line sending end voltage derivation · Power System Analysis I, chapter 5
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
All Transmission and Distribution System Design chapter 7 questions →