- Asked 3/20
- 2072 Asoj · 10 marks
LT feeder options: loss and voltage drop, 50 kW
Short answer
For uniformly distributed load, per-feeder current and length determine loss (∝ I²l) and drop (∝ Il). Option I (4 feeders × 2 km): 8.95% peak power loss, 10.06% max voltage drop. Option II (2 feeders × 4 km): 35.81% loss, 40.23% drop.
A particular load center has a peak demand of 50 kW at a power factor of 0.8 lagging. For the following two cases of 3 phase LT feeder configuration at distribution transformer, compute the % peak power loss and maximum percentage voltage drop in LT. Option I: 4 feeders each of length 2 km. Option II: 2 feeders each of length 4 km. The resistance and reactance per phase of LT conductors are 1.1 Ω/km and 0.25 Ω/km. Assume uniformly distributed load along the feeders. The distribution transformer is rated 11/0.4 kV.
Formulas (uniformly distributed load, 3-phase)
For each feeder of length carrying sending-end current :
The peak load is shared equally between the feeders.
Given: kW, p.f. 0.8 (), V (secondary of 11/0.4 kV), /km, /km. /km.
Option I: 4 feeders × 2 km
Option II: 2 feeders × 4 km
Comparison
| Option | I per feeder | % peak loss | % max drop |
|---|---|---|---|
| I: 4 × 2 km | 22.55 A | 8.95 % | 10.06 % |
| II: 2 × 4 km | 45.11 A | 35.81 % | 40.23 % |
Going from option I to option II doubles both the current and the length of each feeder. The loss per feeder () rises 8 times, and with half as many feeders the total loss rises 4 times; the drop () rises 4 times. Option I is clearly better, but even it exceeds the usual LT drop limit (about 5–8 %), suggesting a bigger conductor or more feeders/transformers.
Answer: Option I: 8.95 % loss, 10.06 % drop; Option II: 35.81 % loss, 40.23 % drop.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- LT loss and voltage drop, 60 kW four feeders · Transmission and Distribution System Design, chapter 7 · asked 3×
- Peak loss and voltage drop for LT feeder options · Transmission and Distribution System Design, chapter 7 · asked 2×
- Distribution loss and voltage drop, four LT feeders · Transmission and Distribution System Design, chapter 7
- LT loss and voltage drop, four 2 km feeders · Transmission and Distribution System Design, chapter 7 · asked 2×
- Peak demand of load center from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
All Transmission and Distribution System Design chapter 7 questions →