Distribution loss and voltage drop, four LT feeders

Short answer

Each feeder carries 10 kW, current 17.88 A, R=1.35 Ω, X=0.375 Ω. Line loss per feeder = I²R = 431 W, total LT loss 1.73 kW; with transformer loss 0.68 kW, total 2.41 kW, %loss = 6.01%. Voltage drop = (√3×17.88×(1.35×0.85+0.375×0.5268))/2 = 20.8 V, 5.48%.

A particular load center has a peak demand of 40 kW at pf of 0.85 lagging. The distribution transformer having 200 watt iron loss and 480 watt copper loss is used to supply four 3 phase LT feeders at 380 V of equal length of 1.5 km each. If LT feeder conductor has resistance and reactance of 0.9 ohm per km and 0.25 determine (i) % Distribution loss (ii) % voltage drop in LT line.

Assumptions:

  • The 40 kW peak is shared equally by the four feeders (10 kW each) and the load is uniformly distributed along each feeder.
  • The reactance is 0.25 Ω/km per phase.
  • The transformer iron loss (200 W) and copper loss (480 W) are the losses at this peak load (the transformer rating is not given).
  • % distribution loss is taken as peak power loss as a percentage of peak demand.

Step 1: Current in each feeder

I=P3Vcos⁡ϕ=10,0003×380×0.85=17.875 AI = \frac{P}{\sqrt{3} V \cos\phi} = \frac{10{,}000}{\sqrt{3} \times 380 \times 0.85} = 17.875 \text{ A}

Step 2: Feeder impedance

R=0.9×1.5=1.35 Ω,X=0.25×1.5=0.375 Ωsin⁡ϕ=1−0.852=0.5268\begin{aligned} R &= 0.9 \times 1.5 = 1.35\ \Omega, \quad X = 0.25 \times 1.5 = 0.375\ \Omega \\ \sin\phi &= \sqrt{1 - 0.85^2} = 0.5268 \end{aligned}

Step 3: LT line loss

For uniformly distributed load, loss = 1/3 of the end-loaded value:

Ploss,feeder=3I2R3=I2R=17.8752×1.35=431.33 WPloss,LT=4×431.33=1725.31 W\begin{aligned} P_{loss,feeder} &= \frac{3 I^2 R}{3} = I^2 R = 17.875^2 \times 1.35 = 431.33 \text{ W} \\ P_{loss,LT} &= 4 \times 431.33 = 1725.31 \text{ W} \end{aligned}

Step 4: Total distribution loss

Ploss=1725.31+200+480=2405.31 W% loss=2405.3140,000×100=6.01%\begin{aligned} P_{loss} &= 1725.31 + 200 + 480 = 2405.31 \text{ W} \\ \%\text{ loss} &= \frac{2405.31}{40{,}000} \times 100 = 6.01\% \end{aligned}

(LT line alone: 4.31%; transformer: 1.70%. On the basis of input power, 2405.31/42,405.31=5.67%2405.31/42{,}405.31 = 5.67\%.)

Step 5: Voltage drop in LT line

For uniformly distributed load, drop = 1/2 of the end-loaded value:

ΔVL=3 I(Rcos⁡ϕ+Xsin⁡ϕ)2=3×17.875×(1.35×0.85+0.375×0.5268)2=3×17.875×1.34502=20.82 V%ΔV=20.82380×100=5.48%\begin{aligned} \Delta V_L &= \frac{\sqrt{3}\, I (R\cos\phi + X\sin\phi)}{2} \\ &= \frac{\sqrt{3} \times 17.875 \times (1.35 \times 0.85 + 0.375 \times 0.5268)}{2} \\ &= \frac{\sqrt{3} \times 17.875 \times 1.3450}{2} = 20.82 \text{ V} \\ \%\Delta V &= \frac{20.82}{380} \times 100 = 5.48\% \end{aligned}

Answer:

  • (i) % distribution loss ≈ 6.01% of peak demand (2.41 kW)
  • (ii) % voltage drop in each LT feeder ≈ 5.48% (20.82 V)

The voltage drop is within the usual ±10% LT limit (and close to a 5% limit), and losses are acceptable.

✓ Answer checked by Claude Opus 5.5 (high effort)