- 2078 Chaitra · 10 marks
Distribution loss and voltage drop, four LT feeders
Short answer
Each feeder carries 10 kW, current 17.88 A, R=1.35 Ω, X=0.375 Ω. Line loss per feeder = I²R = 431 W, total LT loss 1.73 kW; with transformer loss 0.68 kW, total 2.41 kW, %loss = 6.01%. Voltage drop = (√3×17.88×(1.35×0.85+0.375×0.5268))/2 = 20.8 V, 5.48%.
A particular load center has a peak demand of 40 kW at pf of 0.85 lagging. The distribution transformer having 200 watt iron loss and 480 watt copper loss is used to supply four 3 phase LT feeders at 380 V of equal length of 1.5 km each. If LT feeder conductor has resistance and reactance of 0.9 ohm per km and 0.25 determine (i) % Distribution loss (ii) % voltage drop in LT line.
Assumptions:
- The 40 kW peak is shared equally by the four feeders (10 kW each) and the load is uniformly distributed along each feeder.
- The reactance is 0.25 Ω/km per phase.
- The transformer iron loss (200 W) and copper loss (480 W) are the losses at this peak load (the transformer rating is not given).
- % distribution loss is taken as peak power loss as a percentage of peak demand.
Step 1: Current in each feeder
Step 2: Feeder impedance
Step 3: LT line loss
For uniformly distributed load, loss = 1/3 of the end-loaded value:
Step 4: Total distribution loss
(LT line alone: 4.31%; transformer: 1.70%. On the basis of input power, .)
Step 5: Voltage drop in LT line
For uniformly distributed load, drop = 1/2 of the end-loaded value:
Answer:
- (i) % distribution loss ≈ 6.01% of peak demand (2.41 kW)
- (ii) % voltage drop in each LT feeder ≈ 5.48% (20.82 V)
The voltage drop is within the usual ±10% LT limit (and close to a 5% limit), and losses are acceptable.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- LT loss and voltage drop, 60 kW four feeders · Transmission and Distribution System Design, chapter 7 · asked 3×
- LT loss and voltage drop, four 2 km feeders · Transmission and Distribution System Design, chapter 7 · asked 2×
- Peak loss and voltage drop for LT feeder options · Transmission and Distribution System Design, chapter 7 · asked 2×
- LT feeder options: loss and voltage drop, 50 kW · Transmission and Distribution System Design, chapter 7 · asked 3×
- Peak demand of load center from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
- Loss and voltage drop, 16 km uniformly varying load · Transmission and Distribution System Design, chapter 7
- PF improvement of 490 kW load with demand charge · Industrial Power Distribution and Illumination, chapter 10 · asked 2×
- Efficiency and loading of 50 kVA transformer at 40 kW · Electrical Machines I, chapter 2
- Voltage regulation of transformer for lagging load · Electrical Machines I, chapter 2
All Transmission and Distribution System Design chapter 7 questions →