- Asked 3/20
- 2067 Chaitra (old course) · 12 marks
LT loss and voltage drop, 60 kW four feeders
Short answer
Each feeder carries 25.32 A. Total three-phase loss = 4 × (25.32² × 1.35) = 3462.6 W, 5.77% of 60 kW. Voltage drop per phase = ½ × 25.32 × 0.919 × 1.5 = 17.45 V, 7.96%.
A particular load center has a peak demand of 60 kW at a power factor of 0.9. The distribution transformer has four 3-phase LT feeders at 380 V of equal length of 1.5 km each. If the per phase resistance and reactance of LT conductors are 0.9 Ω/km and 0.25 Ω/km, determine the following: i) LT percentage peak power loss ii) Maximum percentage voltage drop in LT. Assume uniformly distributed load along the feeders.
Formulas (uniformly distributed load, 3-phase)
For each feeder of length carrying sending-end current :
The peak load is shared equally between the feeders.
Data
| Quantity | Value |
|---|---|
| Peak demand | 60 kW |
| Power factor | 0.9 () |
| Feeders | 4, each 1.5 km |
| LT voltage | 380 V |
| r, x | 0.9, 0.25 Ω/km |
Current per feeder
i) LT percentage peak power loss
Resistance per phase per feeder .
ii) Maximum percentage voltage drop
Line-to-line drop V.
Why the UDL factors
- The current falls linearly from at the transformer to zero at the end, so the drop equals that of the full current flowing over half the length ().
- Loss integrates , giving one-third of the lumped value; for three phases, .
The drop (≈ 8 %) is at the upper end of the usual LT limit, and the loss (≈ 5.8 %) is acceptable but could be reduced with a larger conductor.
Answer: i) LT peak power loss = 5.77 % ii) Maximum voltage drop = 7.96 %.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- LT loss and voltage drop, four 2 km feeders · Transmission and Distribution System Design, chapter 7 · asked 2×
- LT feeder options: loss and voltage drop, 50 kW · Transmission and Distribution System Design, chapter 7 · asked 3×
- Distribution loss and voltage drop, four LT feeders · Transmission and Distribution System Design, chapter 7
- Peak loss and voltage drop for LT feeder options · Transmission and Distribution System Design, chapter 7 · asked 2×
- Peak demand of load center from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
- Loss and voltage drop, 16 km uniformly varying load · Transmission and Distribution System Design, chapter 7
All Transmission and Distribution System Design chapter 7 questions →