Short answer

Each feeder carries 25.32 A. Total three-phase loss = 4 × (25.32² × 1.35) = 3462.6 W, 5.77% of 60 kW. Voltage drop per phase = ½ × 25.32 × 0.919 × 1.5 = 17.45 V, 7.96%.

A particular load center has a peak demand of 60 kW at a power factor of 0.9. The distribution transformer has four 3-phase LT feeders at 380 V of equal length of 1.5 km each. If the per phase resistance and reactance of LT conductors are 0.9 Ω/km and 0.25 Ω/km, determine the following: i) LT percentage peak power loss ii) Maximum percentage voltage drop in LT. Assume uniformly distributed load along the feeders.

Formulas (uniformly distributed load, 3-phase)

For each feeder of length ll carrying sending-end current II:

PL=3⋅13I2rl=I2rlVD,ph=12I(rcos⁡ϕ+xsin⁡ϕ) l%VD=VD,phVL/3×100\begin{aligned} P_L &= 3\cdot\frac13 I^2 r l = I^2 r l\\ V_{D,ph} &= \frac12 I(r\cos\phi + x\sin\phi)\,l\\ \%V_D &= \frac{V_{D,ph}}{V_L/\sqrt3}\times100 \end{aligned}

The peak load is shared equally between the feeders.

Data

QuantityValue
Peak demand60 kW
Power factor0.9 (sin⁡ϕ=0.4359\sin\phi = 0.4359)
Feeders4, each 1.5 km
LT voltage380 V
r, x0.9, 0.25 Ω/km

Current per feeder

Pfeeder=604=15 kW,I=15 0003×380×0.9=25.32 AP_{feeder} = \frac{60}{4} = 15\ \text{kW},\quad I = \frac{15\,000}{\sqrt3\times380\times0.9} = 25.32\ \text{A}

i) LT percentage peak power loss

Resistance per phase per feeder R=0.9×1.5=1.35 ΩR = 0.9\times1.5 = 1.35\ \Omega.

PL,feeder=I2R=25.322×1.35=865.65 WPL,total=4×865.65=3462.6 W%PL=3462.660 000×100=5.77 %\begin{aligned} P_{L,feeder} &= I^2R = 25.32^2\times1.35 = 865.65\ \text{W}\\ P_{L,total} &= 4\times865.65 = 3462.6\ \text{W}\\ \%P_L &= \frac{3462.6}{60\,000}\times100 = 5.77\ \% \end{aligned}

ii) Maximum percentage voltage drop

rcos⁡ϕ+xsin⁡ϕ=0.9(0.9)+0.25(0.4359)=0.919 Ω/kmVD,ph=12×25.32×0.919×1.5=17.45 VVph=380/3=219.39 V%VD=17.45219.39×100=7.96 %\begin{aligned} r\cos\phi + x\sin\phi &= 0.9(0.9) + 0.25(0.4359) = 0.919\ \Omega/\text{km}\\ V_{D,ph} &= \frac12\times25.32\times0.919\times1.5 = 17.45\ \text{V}\\ V_{ph} &= 380/\sqrt3 = 219.39\ \text{V}\\ \%V_D &= \frac{17.45}{219.39}\times100 = 7.96\ \% \end{aligned}

Line-to-line drop =3×17.45=30.23= \sqrt3\times17.45 = 30.23 V.

Why the UDL factors

  • The current falls linearly from II at the transformer to zero at the end, so the drop equals that of the full current flowing over half the length (12Il\frac12 Il).
  • Loss integrates I2I^2, giving one-third of the lumped value; for three phases, 3×13I2rl=I2rl3\times\frac13 I^2 r l = I^2 r l.

The drop (≈ 8 %) is at the upper end of the usual LT limit, and the loss (≈ 5.8 %) is acceptable but could be reduced with a larger conductor.

Answer: i) LT peak power loss = 5.77 % ii) Maximum voltage drop = 7.96 %.