Loss and drop, 15 km 11 kV feeder

Short answer

For a uniformly distributed load, power loss = I_s² r l and voltage drop = ½ I_s z l. With given values, loss = 90 kW, drop = 2294.6 V per phase (3974 V line).

Compute the power loss & voltage drop for a 15 km long 11 kV three phase distribution feeder having sending end current of 100 A with uniformly distributed load. Use z = (0.6 + j3) Ω/km. Derive any expression used in above calculation.

Derivation for uniformly distributed load

Let a feeder of length ll carry sending-end current IsI_s, with load tapped uniformly so the current falls linearly to zero at the far end:

I(x)=Is(1−xl)I(x) = I_s\left(1-\frac{x}{l}\right)

Per-phase voltage drop, with z=r+jxz = r + jx per km:

VD=∫0lzIs(1−xl)dx=12IszlV_D = \int_0^l z I_s\left(1-\frac{x}{l}\right)dx = \frac{1}{2}I_s z l

Three-phase power loss:

PL=3∫0lrIs2(1−xl)2dx=3⋅13Is2rl=Is2rlP_L = 3\int_0^l r I_s^2\left(1-\frac{x}{l}\right)^2dx = 3\cdot\frac{1}{3}I_s^2 r l = I_s^2 r l

So a UDL feeder behaves like the whole load lumped at the middle for voltage drop, and at one-third of the length for loss.

Substitution

Is=100I_s = 100 A, l=15l = 15 km, z=0.6+j3 Ωz = 0.6 + j3\ \Omega/km, ∣z∣=0.62+32=3.059 Ω|z| = \sqrt{0.6^2+3^2} = 3.059\ \Omega/km. No load p.f. is given, so the drop is taken as 12Is∣z∣l\frac12 I_s|z|l (the maximum value).

PL=1002×0.6×15=90,000 W=90 kWVD,ph=12×100×3.059×15=2294.6 VVD,L=3×2294.6=3974.3 V (36.1 % of 11 kV)\begin{aligned} P_L &= 100^2\times0.6\times15 = 90{,}000\ \text{W} = 90\ \text{kW}\\ V_{D,ph} &= \frac{1}{2}\times100\times3.059\times15 = 2294.6\ \text{V}\\ V_{D,L} &= \sqrt3\times2294.6 = 3974.3\ \text{V}\ (36.1\ \%\ \text{of } 11\ \text{kV}) \end{aligned}

Note: a reactance of 3 Ω/km is unusually high for an 11 kV line (typical is about 0.3–0.4 Ω/km). If z=0.6+j0.3z = 0.6 + j0.3 was intended, ∣z∣=0.6708|z| = 0.6708, VD,ph=503.1V_{D,ph} = 503.1 V, VD,L=871.4V_{D,L} = 871.4 V (7.92 %); the loss is unchanged at 90 kW since it depends only on rr.

Answer: Power loss = 90 kW; voltage drop ≈ 2294.6 V per phase (3974 V line) with the given z.