Temporary overvoltage at no load and its remedy
Short answer
No‑load temporary overvoltage is 1.103 pu. To limit to 1.04 pu, install a shunt reactor of 2221 Ω per phase (≈72 MVAr three‑phase) at the receving end.
A 400kV, 50Hz HV 400 km long HV transmission line has r = 0.025 Ω/Km, L = 1mH/Km and C = 12nF/Km. Assuming a perfectly loss less line determine the p.u. temporary over voltage at receiving end under no-load condition. What counter measure must be applied to limit this temporary over voltage at receiving end node to 1.04 p.u?
Treat the line as lossless and find the no-load receiving-end voltage from the long-line equations. This rise is the Ferranti effect.
Data: km, mH/km, nF/km, Hz ( neglected as stated).
Line constants
Temporary overvoltage at no load
With , :
So the receiving end rises to about 1.103 pu (about 441 kV for 400 kV at the sending end).
Countermeasure: shunt reactor at the receiving end
Connect a shunt reactor at the receiving end. Then and
For :
Three-phase rating at rated voltage:
(about 77.9 MVAr at the 1.04 pu operating voltage).
Answer: no-load TOV = 1.103 pu. Install a shunt reactor of about 2221 Ω per phase (≈ 72 MVAr, 3-phase) at the receiving end to limit the voltage to 1.04 pu.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Temporary overvoltage for SLG fault at line end · High Voltage Engineering, chapter 3
- Temporary overvoltage for SLG fault at line middle · High Voltage Engineering, chapter 3
- Mid-line reactor for Vr = Vs at no load · High Voltage Engineering, chapter 3
- Surge impedance and travel time of 400 km line · High Voltage Engineering, chapter 3
- Closing resistance Rs to limit overvoltage to 1.8 pu · High Voltage Engineering, chapter 3
- Charging reactive power of line at no load · High Voltage Engineering, chapter 3 · asked 2×
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- Voltage 150 km along a 400 km line · Power System Analysis I, chapter 5
- Loss and voltage drop, 16 km uniformly varying load · Transmission and Distribution System Design, chapter 7
- Initial line design for 200 MW over 120 km · Transmission and Distribution System Design, chapter 2