Temporary overvoltage at no load and its remedy

Short answer

No‑load temporary overvoltage is 1.103 pu. To limit to 1.04 pu, install a shunt reactor of 2221 Ω per phase (≈72 MVAr three‑phase) at the receving end.

A 400kV, 50Hz HV 400 km long HV transmission line has r = 0.025 Ω/Km, L = 1mH/Km and C = 12nF/Km. Assuming a perfectly loss less line determine the p.u. temporary over voltage at receiving end under no-load condition. What counter measure must be applied to limit this temporary over voltage at receiving end node to 1.04 p.u?

Treat the line as lossless and find the no-load receiving-end voltage from the long-line equations. This rise is the Ferranti effect.

Data: l=400l = 400 km, L=1L = 1 mH/km, C=12C = 12 nF/km, f=50f = 50 Hz (rr neglected as stated).

Line constants

β=ωLC=2π(50)1×10−3×12×10−9=314.16×3.464×10−6=1.0883×10−3 rad/kmβl=1.0883×10−3×400=0.4353 rad=24.94∘Zc=L/C=1×10−312×10−9=288.68 Ω\begin{aligned} \beta &= \omega\sqrt{LC} = 2\pi(50)\sqrt{1\times10^{-3} \times 12\times10^{-9}} \\ &= 314.16 \times 3.464\times10^{-6} = 1.0883\times10^{-3}\ \text{rad/km} \\ \beta l &= 1.0883\times10^{-3} \times 400 = 0.4353\ \text{rad} = 24.94^\circ \\ Z_c &= \sqrt{L/C} = \sqrt{\frac{1\times10^{-3}}{12\times10^{-9}}} = 288.68\ \Omega \end{aligned}

Temporary overvoltage at no load

With Ir=0I_r = 0, Vs=Vrcos⁡βlV_s = V_r\cos\beta l:

VrVs=1cos⁡24.94∘=10.9067=1.1029 pu\frac{V_r}{V_s} = \frac{1}{\cos 24.94^\circ} = \frac{1}{0.9067} = 1.1029\ \text{pu}

So the receiving end rises to about 1.103 pu (about 441 kV for 400 kV at the sending end).

Countermeasure: shunt reactor at the receiving end

Connect a shunt reactor XLX_L at the receiving end. Then Ir=Vr/(jXL)I_r = V_r/(jX_L) and

VsVr=cos⁡βl+ZcXLsin⁡βl\frac{V_s}{V_r} = \cos\beta l + \frac{Z_c}{X_L}\sin\beta l

For Vr/Vs=1.04V_r/V_s = 1.04:

cos⁡βl+ZcXLsin⁡βl=11.04=0.96154ZcXLsin⁡βl=0.96154−0.90674=0.05480XL=288.68×sin⁡24.94∘0.05480=288.68×0.421730.05480=2221.4 Ω per phase\begin{aligned} \cos\beta l + \frac{Z_c}{X_L}\sin\beta l &= \frac{1}{1.04} = 0.96154 \\ \frac{Z_c}{X_L}\sin\beta l &= 0.96154 - 0.90674 = 0.05480 \\ X_L &= \frac{288.68 \times \sin 24.94^\circ}{0.05480} = \frac{288.68 \times 0.42173}{0.05480} \\ &= 2221.4\ \Omega\ \text{per phase} \end{aligned}

Three-phase rating at rated voltage:

Q=V2XL=(400)22221.4=72.0 MVArQ = \frac{V^2}{X_L} = \frac{(400)^2}{2221.4} = 72.0\ \text{MVAr}

(about 77.9 MVAr at the 1.04 pu operating voltage).

Answer: no-load TOV = 1.103 pu. Install a shunt reactor of about 2221 Ω per phase (≈ 72 MVAr, 3-phase) at the receiving end to limit the voltage to 1.04 pu.