Temporary overvoltage for SLG fault at line end

Short answer

Use long-line Ferranti rise and sequence network with Z0=Z1+3Zn; prefault open-end voltage is 1.0845 pu and earth-fault factor is 1.169. Healthy-phase TOV is 1.268 pu, about 293 kV rms to ground, roughly 414 kV peak.

A 400 kV high voltage transmission line has resistance = 0.031 Ω/km, inductance = 1 mH/km and capacitance = 10 nF/km. Compute the temporary over voltage due to single line to ground fault if the fault is at the end of the 400 km long line. Consider the line resistance and generator neutral impedance of 5 + j50 Ω. Neglect fault impedance.

A single line-to-ground (SLG) fault raises the power-frequency voltage of the healthy phases. On an unloaded long line it is raised further by the Ferranti effect. The result is a temporary overvoltage (TOV).

Method and assumptions (data not given are taken as below and stated):

  1. Generator emf E=1E = 1 pu (phase), with the generator's own sequence impedances neglected (not given).
  2. Prefault voltage at the fault point is found from the long-line equation with the far end open (Ferranti rise):
Ef=E cosh⁡γ(l−x)cosh⁡γlE_f = E\,\frac{\cosh\gamma(l - x)}{\cosh\gamma l}

where xx is the distance of the fault from the source. 3. Positive- and negative-sequence impedance up to the fault: Z1=Z2=(r+jωl) xZ_1 = Z_2 = (r + j\omega l)\,x. 4. Zero-sequence impedance Z0=Z1+3ZnZ_0 = Z_1 + 3Z_n. No separate zero-sequence line data are given, so the line's Z0Z_0 is taken equal to Z1Z_1, and ZnZ_n is the generator neutral impedance.

Healthy-phase voltage for an SLG fault on phase aa through ZfZ_f:

Vb=Ef[a2−Z0−Z12Z1+Z0+3Zf]=Ef[a2−ZnZ1+Zn+Zf]V_b = E_f\left[a^2 - \frac{Z_0 - Z_1}{2Z_1 + Z_0 + 3Z_f}\right] = E_f\left[a^2 - \frac{Z_n}{Z_1 + Z_n + Z_f}\right] Vc=Ef[a−ZnZ1+Zn+Zf],a=1∠120∘V_c = E_f\left[a - \frac{Z_n}{Z_1 + Z_n + Z_f}\right], \qquad a = 1\angle120^\circ

Data: r=0.031 Ωr = 0.031\ \Omega/km, L=1L = 1 mH/km, C=10C = 10 nF/km, length 400 km, fault at the far end (x=400x = 400 km), Zn=5+j50 ΩZ_n = 5 + j50\ \Omega, Zf=0Z_f = 0. Line resistance is included, as asked.

Step 1: line constants

z=0.031+j(314.16)(1×10−3)=0.031+j0.31416 Ω/kmy=j(314.16)(10×10−9)=j3.1416×10−6 S/kmγ=zy=(0.04896+j0.99466)×10−3 /kmZc=z/y=316.6−j15.6 Ωβl=0.9947×10−3×400=0.3974 rad=22.77∘\begin{aligned} z &= 0.031 + j(314.16)(1\times10^{-3}) = 0.031 + j0.31416\ \Omega/\text{km} \\ y &= j(314.16)(10\times10^{-9}) = j3.1416\times10^{-6}\ \text{S/km} \\ \gamma &= \sqrt{zy} = (0.04896 + j0.99466)\times10^{-3}\ /\text{km} \\ Z_c &= \sqrt{z/y} = 316.6 - j15.6\ \Omega \\ \beta l &= 0.9947\times10^{-3}\times400 = 0.3974\ \text{rad} = 22.77^\circ \end{aligned}

Step 2: prefault voltage at the open end (Ferranti)

Ef=1∣cosh⁡γl∣=1.0845 pu(lossless: 1/cos⁡22.77∘=1.0845)E_f = \frac{1}{|\cosh\gamma l|} = 1.0845\ \text{pu} \quad (\text{lossless: } 1/\cos 22.77^\circ = 1.0845)

Step 3: sequence impedances up to the fault

Z1=Z2=400(0.031+j0.31416)=12.4+j125.66 ΩZ0=Z1+3Zn=27.4+j275.66 ΩZ1+Zn=17.4+j175.66 Ωm=ZnZ1+Zn=5+j5017.4+j175.66=0.2847∠−0.05∘\begin{aligned} Z_1 &= Z_2 = 400(0.031 + j0.31416) = 12.4 + j125.66\ \Omega \\ Z_0 &= Z_1 + 3Z_n = 27.4 + j275.66\ \Omega \\ Z_1 + Z_n &= 17.4 + j175.66\ \Omega \\ m &= \frac{Z_n}{Z_1 + Z_n} = \frac{5 + j50}{17.4 + j175.66} = 0.2847\angle{-0.05^\circ} \end{aligned}

Step 4: healthy-phase voltages

Vb/Ef=a2−m=−0.7847−j0.8658,∣Vb/Ef∣=1.1684Vc/Ef=a−m=−0.7847+j0.8663,∣Vc/Ef∣=1.1688\begin{aligned} V_b/E_f &= a^2 - m = -0.7847 - j0.8658, \quad |V_b/E_f| = 1.1684 \\ V_c/E_f &= a - m = -0.7847 + j0.8663, \quad |V_c/E_f| = 1.1688 \end{aligned}

Step 5: temporary overvoltage

VTOV=1.1688×1.0845=1.2676 pu=1.2676×4003=292.7 kV (rms, phase)\begin{aligned} V_{TOV} &= 1.1688 \times 1.0845 = 1.2676\ \text{pu} \\ &= 1.2676 \times \frac{400}{\sqrt3} = 292.7\ \text{kV (rms, phase)} \end{aligned}
QuantityValue
Ferranti factor at the open end1.0845
Z0/Z1Z_0/Z_1 (magnitude)2.19
Earth-fault factor1.169
TOV on healthy phase1.268 pu ≈ 292.7 kV rms
 Gen ~--[ 400 km line ]--x  SLG at far end
  |                          (phase a)
 Zn = 5+j50 ohm
  |
 gnd

Answer: the temporary overvoltage on the healthy phases ≈ 1.27 pu (≈ 293 kV rms to ground, peak ≈ 414 kV). This is the Ferranti rise (1.085) multiplied by the earth-fault factor (1.169). Since X0/X1<3X_0/X_1 < 3 here, the system behaves as effectively grounded (earth-fault factor below 1.4).