Healthy-phase overvoltage in SLG fault; effective grounding
Short answer
For an SLG fault with Z1=Z2=jX1 and Z0=jX0, k=X0/X1, healthy phase voltage is |Vb|/Ea = sqrt(3) sqrt(k^2+k+1)/(k+2). Effective grounding requires coefficient of earthing not exceed 0.8, giving k <= 5.16. Practical standard is X0/X1 <= 3 and R0/X1 <= 1.
Derive the relation for over voltage in healthy phase when unsymmetrical single line to ground fault occurs in transmission line. Also derive the condition of effective grounding. (X0 = 5.16 X1).
During a single line-to-ground (SLG) fault on phase , the voltages of the healthy phases and rise above normal. How much they rise depends on how the system neutral is grounded, that is, on the ratio .
Derivation of the healthy-phase voltage
Fault on phase (zero fault impedance): , . From symmetrical components:
The sequence voltages at the fault are
Phase voltage, using :
Neglect resistance and take , , . Then and , so
With :
is the same by symmetry.
| (pu of phase voltage) | |
|---|---|
| 1 (solid grounding) | 1.00 |
| 3 | 1.25 |
| 5.16 | 1.385 |
| (isolated) |
Condition of effective grounding
The coefficient of earthing (COE) is the highest healthy-phase voltage during an SLG fault, as a fraction of the line-to-line voltage:
A system is effectively grounded when COE ≤ 80%, that is, .
So, with resistance neglected, the limiting case is . Check: gives pu, which is 80% of line voltage. This is exactly the limit of effective grounding.
In practice resistance also raises the overvoltage. So standards (IEEE/IEC) define effective grounding as
which keeps COE ≤ 80% with a margin. This allows 80% arresters (rated at 80% of line voltage) and reduced insulation levels.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Temporary overvoltage for SLG fault at line middle · High Voltage Engineering, chapter 3
- Temporary overvoltage for SLG fault at line end · High Voltage Engineering, chapter 3
- Switching overvoltage with trapped charge and Rs · High Voltage Engineering, chapter 3 · asked 3×
- Closing resistance Rs to limit overvoltage to 1.8 pu · High Voltage Engineering, chapter 3
- SLG fault at bus 3, currents and voltages · Power System Analysis II, chapter 5
- SLG fault at mid-line through 4.033 Ω · Power System Analysis II, chapter 5
- SLG fault on 20 MVA generator · Power System Analysis II, chapter 5
- SLG fault: sequence networks in series · Power System Analysis II, chapter 5 · asked 5×