Healthy-phase overvoltage in SLG fault; effective grounding

Short answer

For an SLG fault with Z1=Z2=jX1 and Z0=jX0, k=X0/X1, healthy phase voltage is |Vb|/Ea = sqrt(3) sqrt(k^2+k+1)/(k+2). Effective grounding requires coefficient of earthing not exceed 0.8, giving k <= 5.16. Practical standard is X0/X1 <= 3 and R0/X1 <= 1.

Derive the relation for over voltage in healthy phase when unsymmetrical single line to ground fault occurs in transmission line. Also derive the condition of effective grounding. (X0 = 5.16 X1).

During a single line-to-ground (SLG) fault on phase aa, the voltages of the healthy phases bb and cc rise above normal. How much they rise depends on how the system neutral is grounded, that is, on the ratio X0/X1X_0/X_1.

Derivation of the healthy-phase voltage

Fault on phase aa (zero fault impedance): Va=0V_a = 0, Ib=Ic=0I_b = I_c = 0. From symmetrical components:

Ia1=Ia2=Ia0=EaZ1+Z2+Z0I_{a1} = I_{a2} = I_{a0} = \frac{E_a}{Z_1 + Z_2 + Z_0}

The sequence voltages at the fault are

Va1=Ea−Ia1Z1,Va2=−Ia1Z2,Va0=−Ia1Z0V_{a1} = E_a - I_{a1}Z_1, \quad V_{a2} = -I_{a1}Z_2, \quad V_{a0} = -I_{a1}Z_0

Phase bb voltage, using a2+a+1=0a^2 + a + 1 = 0:

Vb=Va0+a2Va1+aVa2=a2Ea−Ia1(Z0+a2Z1+aZ2)\begin{aligned} V_b &= V_{a0} + a^2V_{a1} + aV_{a2} \\ &= a^2E_a - I_{a1}(Z_0 + a^2Z_1 + aZ_2) \end{aligned}

Neglect resistance and take Z1=Z2=jX1Z_1 = Z_2 = jX_1, Z0=jX0Z_0 = jX_0, k=X0/X1k = X_0/X_1. Then Z0+a2Z1+aZ2=jX1(k−1)Z_0 + a^2Z_1 + aZ_2 = jX_1(k - 1) and Ia1=Ea/[jX1(k+2)]I_{a1} = E_a/[jX_1(k+2)], so

Vb=Ea[a2−k−1k+2]V_b = E_a\left[a^2 - \frac{k-1}{k+2}\right]

With a2=−12−j32a^2 = -\tfrac{1}{2} - j\tfrac{\sqrt3}{2}:

Vb=Ea[−3k2(k+2)−j32]V_b = E_a\left[-\frac{3k}{2(k+2)} - j\frac{\sqrt3}{2}\right] ∣Vb∣Ea=3k2+k+1k+2\boxed{\frac{|V_b|}{E_a} = \frac{\sqrt3\sqrt{k^2 + k + 1}}{k + 2}}

∣Vc∣|V_c| is the same by symmetry.

k=X0/X1k = X_0/X_1VbV_b (pu of phase voltage)
1 (solid grounding)1.00
31.25
5.161.385
∞\infty (isolated)3=1.732\sqrt3 = 1.732

Condition of effective grounding

The coefficient of earthing (COE) is the highest healthy-phase voltage during an SLG fault, as a fraction of the line-to-line voltage:

COE=Vb,max3Ea\text{COE} = \frac{V_{b,max}}{\sqrt3E_a}

A system is effectively grounded when COE ≤ 80%, that is, Vb≤0.83Ea=1.386EaV_b \le 0.8\sqrt3 E_a = 1.386E_a.

3k2+k+1k+2≤0.83k2+k+1≤0.64(k+2)20.36k2−1.56k−1.56≤0k≤5.17\begin{aligned} \frac{\sqrt3\sqrt{k^2+k+1}}{k+2} &\le 0.8\sqrt3 \\ k^2 + k + 1 &\le 0.64(k+2)^2 \\ 0.36k^2 - 1.56k - 1.56 &\le 0 \\ k &\le 5.17 \end{aligned}

So, with resistance neglected, the limiting case is X0≈5.16X1X_0 \approx 5.16X_1. Check: k=5.16k = 5.16 gives Vb=332.79/7.16=1.385V_b = \sqrt3\sqrt{32.79}/7.16 = 1.385 pu, which is 80% of line voltage. This is exactly the limit of effective grounding.

In practice resistance also raises the overvoltage. So standards (IEEE/IEC) define effective grounding as

X0X1≤3andR0X1≤1\frac{X_0}{X_1} \le 3 \quad \text{and} \quad \frac{R_0}{X_1} \le 1

which keeps COE ≤ 80% with a margin. This allows 80% arresters (rated at 80% of line voltage) and reduced insulation levels.