- Asked 3/20
- 2066 Magh (old course) · 8+8 marks
Switching overvoltage with trapped charge and Rs
Short answer
Use series RLC step response with trapped charge -1 pu; maximum is 1+2 exp(-alpha pi/omega). Without Rs it is 2.90 pu; to limit to 1.8 pu, total R must be 177.1 ohm, so Rs is about 167 ohm.
Using the single-phase equivalent lumped parameter model circuit of a 3 phase, 400 kV, 50 Hz, 400 km long EHV transmission line shown below in figure, compute: a) The maximum per unit switching over voltage while closing the main CB without external switching resistance Rs considering the trap charge across the capacitor as −1 pu. b) Switching resistance Rs to be inserted during the closing of the CB so that the maximum switching over voltage in part (a) will be limited to 1.8 pu. [Figure: AC source feeding the line through the main circuit breaker (CB); a resistor Rs in series with an auxiliary CB is connected in parallel with the main CB; series line impedance 10 Ω and 0.5 H to the receiving end Vo; shunt capacitor 5 μF from Vo to ground] Switching over voltage is given as (E − V0)[1 − e^(−αt) (√(α² + ω²)/ω) cos(ωt − φ)] + V0, where tan φ = α/ω, φ = tan⁻¹(α/ω).
When the breaker closes, the lumped circuit is a series R–L–C circuit driven by a step (closing at the source peak, pu). The capacitor starts at the trapped-charge voltage . The given response is
with and .
Setting gives , so the first and largest peak is at . There, and . Hence
With pu and pu:
Circuit data: , H, F (source resistance neglected).
(a) Without
The peak occurs at ms.
(b) to limit the overvoltage to 1.8 pu
Using :
Check: , so pu ✓
E ~---+--- main CB ---+--10 ohm--0.5 H--+-- Vo
| | |
+--Rs--aux CB---+ 5 uF (V0=-1 pu)
|
----------------------------------------+-- gnd
| Case | Total R () | (pu) |
|---|---|---|
| (a) no | 10 | 2.90 |
| (b) with | 177.09 | 1.80 |
Answer: (a) 2.90 pu; (b) 167 Ω. In practice the pre-insertion resistor is bypassed by the main contacts after about 8–10 ms.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Switching resistance Rs for 1.8 pu limit · High Voltage Engineering, chapter 3 · asked 3×
- Lumped line energisation with trapped charge · High Voltage Engineering, chapter 3
- Closing resistance Rs to limit overvoltage to 1.8 pu · High Voltage Engineering, chapter 3
- Charge matrix of 400 kV line · High Voltage Engineering, chapter 5
- Surge impedance and travel time of 400 km line · High Voltage Engineering, chapter 3
- Temporary overvoltage for SLG fault at line middle · High Voltage Engineering, chapter 3
- RI levels of 400 kV line at 1 MHz · High Voltage Engineering, chapter 5
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- Equivalent-T of 300 km long line · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×