Lumped line energisation with trapped charge
Short answer
Attenuation factor a = R/(2L) = 15.5 s⁻¹. Damped natural frequency ω = 790.4 rad/s, f = 125.8 Hz. Peak capacitor voltage is 665.5 kV with no trapped charge and 988.0 kV with -343 kV trapped charge (opposite polarity).
A 400-kV 400-km line has the distributed parameters r = 0.031 Ω/km, l = 1 mH/km, and c = 10 nF/km. The equivalent lumped parameters for the circuit are assumed as R = 12.4 Ω, L = 400 mH, and C = 4 μF. It is excited by an equivalent step voltage of magnitude E = 420√2/√3 = 343 kV. Calculate (i) the attenuation factor a, (ii) the natural angular frequency and frequency, and (iii) the peak value of voltage across C with the line holding of • no trapped charge and • an initial trapped-charge voltage of 343 kV.
The line is represented by a series –– circuit energised by a step kV. Given , H, F.
(i) Attenuation factor
(ii) Natural angular frequency and frequency
Undamped:
Damped:
(Since , the circuit is oscillatory.)
(iii) Peak voltage across C
The capacitor voltage reaches its first peak at ms:
Damping factor:
(a) No trapped charge ():
(b) Trapped charge of 343 kV. The worst (and usual textbook) case is reclosing when the trapped charge is of opposite polarity to the source, kV:
If the trapped charge had the same polarity ( kV), and there is no oscillation: kV.
Answer: ; rad/s, Hz; kV with no trapped charge and kV with 343 kV trapped charge of opposite polarity.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Switching overvoltage with trapped charge and Rs · High Voltage Engineering, chapter 3 · asked 3×
- Charge matrix of 400 kV line · High Voltage Engineering, chapter 5
- Surge impedance and travel time of 400 km line · High Voltage Engineering, chapter 3
- Inductance of 420 kV line, transposed and untransposed · High Voltage Engineering, chapter 5
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- RI levels of 400 kV line at 1 MHz · High Voltage Engineering, chapter 5
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.95 pf · Power System Analysis I, chapter 5
- Equivalent-T of 300 km long line · Power System Analysis I, chapter 5
- Voltage 150 km along a 400 km line · Power System Analysis I, chapter 5