Closing resistance Rs to limit overvoltage to 1.8 pu
Short answer
Insert 34.7 Ω as the switching resistor in series during closing. With total circuit resistance 44.81 Ω, the maximum overvoltage is limited to 1.8 pu.
Using the single phase equivalent lumped parameter model circuit of 3-phase, 400kV, 50Hz, 400 km long EHV line shown below, compute the switching resistance Rs to be inserted during the closing of circuit breaker so that maximum switching overvoltage will be limited to 1.8 pu. [Figure: source Vs with 0.12 Ω internal resistance feeds circuit breaker CB; resistor Rs with its own switch is connected in parallel with CB; series line impedance 10 Ω + 0.5 H to receiving node Vo; shunt capacitor 5 μF from Vo to ground]
When the breaker closes, the line acts as a series R–L–C circuit excited by a step voltage (closing at the peak of the source voltage, 1 pu). With no trapped charge, the capacitor voltage is
Setting gives , so the first (largest) peak is at :
Data: H, F. Total resistance (source + line + switching resistor in series during closing).
Without (for reference)
, so and rad/s.
Required for 1.8 pu
Using :
Check: with , , so pu ✓
Vs ~--0.12--+--CB--+--10 ohm--0.5 H--+-- Vo
| | |
+-Rs-/-+ 5 uF
|
-------------------------------------+-- gnd
The resistor is in circuit only for the first few milliseconds (the pre-insertion time). The main contacts then short it out, which produces a second, smaller transient.
Answer: 34.7 Ω (total circuit resistance 44.81 Ω), assuming no trapped charge and closing at the voltage peak.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Switching resistance Rs for 1.8 pu limit · High Voltage Engineering, chapter 3 · asked 3×
- Switching overvoltage with trapped charge and Rs · High Voltage Engineering, chapter 3 · asked 3×
- Equivalent-T of 300 km long line · Power System Analysis I, chapter 5
- Equivalent-π model of a long line · Power System Analysis I, chapter 5
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5