Switching resistance Rs for 1.8 pu limit
Short answer
Using series RLC step response, set Vmax = E(1+e^{-απ/ω}) = 1.8 pu. Solving yields required total resistance RT = 44.81 Ω, so Rs = RT - 10 = 34.8 Ω limits the switching overvoltage to 1.8 pu.
Using the single phase equivalent lumped parameter model circuit of a 3-phase, 400 kV, 50 Hz, 400 km long EHV transmission line shown below, compute the switching resistance Rs to be inserted during the closing of the CB so that the max switching over voltage will be limited to 1.8 pu. [Figure: AC source feeding the line through the main circuit breaker (CB); a resistor Rs in series with an auxiliary CB is connected in parallel with the main CB; series line impedance 10 Ω and 0.5 H to the receiving end Vo; shunt capacitor 5 μF from Vo to ground]
Assumptions: the line is represented by the given single-phase lumped series –– circuit; the breaker closes at the peak of the source voltage (worst case), the line has no trapped charge, and 1 pu = peak of source phase voltage. When the auxiliary breaker closes first, is in series with the line resistance.
Given: , H, F.
Formula
For energisation of a series circuit by a step with :
where . Also
Overvoltage without (check)
, rad/s
which exceeds 1.8 pu, so a resistor is needed.
Required total resistance
Let . From :
Switching resistance
Check: , rad/s, pu.
Answer: (total series resistance 44.8 Ω) limits the maximum switching overvoltage to 1.8 pu. After a short insertion time (about 8–10 ms) the main CB closes and shorts .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Switching overvoltage with trapped charge and Rs · High Voltage Engineering, chapter 3 · asked 3×
- Closing resistance Rs to limit overvoltage to 1.8 pu · High Voltage Engineering, chapter 3
- Surge impedance and travel time of 400 km line · High Voltage Engineering, chapter 3
- Lumped line energisation with trapped charge · High Voltage Engineering, chapter 3
- RI levels of 400 kV line at 1 MHz · High Voltage Engineering, chapter 5
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- Equivalent-T of 300 km long line · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6