- 2068 Bhadra (old course) · 8 marks
Transformer BIL and arrester resistance for 500 kV line
Short answer
Transformer BIL is 1664 kV (standard 1675 kV). For a 5 kA lightning stroke, arrester current is 6.70 kA and arrester resistance is 177.4 Ω. If 5 kA is the arrester discharge current, resistance is 237.7 Ω.
A 500 kV EHV transmission line with surge impedance of 360 Ω is effectively grounded. If the arrestor protective ratio is 2.83, determine the basic insulation withstand voltage level of the transformer for a protective ratio margin is 1.4. Also determine the arrestor resistance for a lightning stroke of 5 kA.
The transformer BIL is obtained from the arrester protective level and the required margin. The arrester resistance is then found from the travelling-wave current through the arrester during the stroke.
Assumptions
- Highest system voltage = kV (rms, line-to-line).
- Effectively grounded: arrester rating = 80% of highest system voltage.
- Arrester protective ratio = protective level (peak) / rated voltage (rms).
- The 5 kA stroke current travels on the line, producing a voltage wave .
Step 1: Arrester rating and protective level
Step 2: BIL of the transformer
The next standard BIL, 1675 kV, would be chosen.
Step 3: Arrester resistance for a 5 kA stroke
Voltage wave on the line:
Arrester current (line terminated by the arrester at voltage ):
Arrester resistance:
(If 5 kA is taken directly as the arrester discharge current, .)
| Quantity | Value |
|---|---|
| Highest system voltage | 525 kV |
| Arrester rating | 420 kV rms |
| Protective level | 1188.6 kV |
| Transformer BIL | 1664 kV (1675 kV standard) |
| Arrester current | 6.70 kA |
| Arrester resistance | 177.4 Ω |
Answer: BIL ≈ 1664 kV (use 1675 kV); arrester resistance ≈ 177.4 Ω (237.7 Ω if 5 kA is the arrester current itself).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer BIL and maximum arrester distance · High Voltage Engineering, chapter 4
- Arrester separation for a 500 kV/μs surge · High Voltage Engineering, chapter 4
- Arrester with 1600 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester with 1000 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester with 1000 kV BIL on 350 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester current, resistance and rating on 132 kV line · High Voltage Engineering, chapter 4
- T/F: switching surge ratio vs system voltage · Transmission and Distribution System Design, chapter 3 · asked 4×
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 360 m head plant, 132 kV · Power Plant Design, chapter 4 · asked 5×
- Driving point impedance and voltage ratio, two 0.5 F · Electrical Circuit Theory, chapter 5