- 2073 Bhadra · 8 marks
Arrester with 1000 kV BIL on 300 Ω line
Short answer
Incident current is 4200/300 = 14 kA. Reflected voltage = 1000-4200 = -3200 kV, reflected current = 3200/300 = 10.67 kA. Arrester discharge current = 14+10.67 = 24.67 kA, resistance = 1000/24.67 = 40.54 Ω.
A lightning arrester with BIL rating of 1000 kV located at the end of the line having surge impedance of 300 Ω receives a travelling wave of 4200 kV. Determine (i) reflected voltage and current at the arrester location (ii) arrester discharge current and resistance offered by the arrester.
When the travelling wave reaches the arrester at the line end, the arrester conducts and holds the voltage at its rated (protective) level of 1000 kV. The arrester acts as a resistance , so part of the wave is reflected.
Data
- Incident voltage, kV
- Arrester voltage (BIL rating / protective level), kV
- Surge impedance,
Incident current
(i) Reflected voltage and current
Voltage at the arrester = incident + reflected:
The reflected voltage is negative (it cancels most of the incident wave), and the reflected current is positive (it adds to the incident current).
(ii) Arrester discharge current and resistance
Check with reflection coefficient
| Quantity | Value |
|---|---|
| Incident current | 14 kA |
| Reflected voltage | −3200 kV |
| Reflected current | +10.67 kA |
| Arrester current | 24.67 kA |
| Arrester resistance | 40.54 Ω |
Answer: kV, kA, kA, .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Arrester with 1000 kV BIL on 350 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester with 1600 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester current, resistance and rating on 132 kV line · High Voltage Engineering, chapter 4
- Transformer BIL and maximum arrester distance · High Voltage Engineering, chapter 4
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- Arrester current and resistance for 750 kV line · High Voltage Engineering, chapter 4 · asked 2×
- Arrester separation for a 500 kV/μs surge · High Voltage Engineering, chapter 4
- Surge on 400 Ω line terminated by 1000 Ω · High Voltage Engineering, chapter 3