Transformer BIL and maximum arrester distance

Short answer

Transformer BIL = 1.25×1008 = 1260 kV (standard 1300 kV). Using assumed surge steepness 3000 kV/μs, maximum distance L = (1260-1008)×300/(2×3000) = 12.6 m to limitt transformer voltage to BIL.

A 400 kV line shown in figure below is effectively grounded which is protected by L.A. with PR = 3. The transformer has its protection ratio (TPR) = 1.25 with Zc = 350 Ω. Determine BIL of Tr. Also find the maximum distance between transformer and lightning arrestor so that the insulation co-ordination is properly met. [Figure: 400 kV surge travelling on a line of Z0 = 300 Ω reaches an arrester connected to ground; the transformer (Z0 = 350 Ω) is 30 m beyond the arrester; α and β mark the transmitted and reflected waves at the transformer]

The transformer BIL is fixed from the arrester protective level and the transformer protective ratio. The maximum separation is then the distance at which the extra voltage built up between arrester and transformer just uses up the margin between BIL and the arrester protective level.

Assumptions

  • Highest system voltage of a 400 kV system = 1.05×400=4201.05 \times 400 = 420 kV (line-to-line, rms).
  • Effectively grounded system: coefficient of earthing 0.8, so arrester rating = 80% of highest system voltage.
  • "PR = 3" of the arrester is the ratio of its protective level (peak) to its rated voltage (rms).
  • The figure gives no surge steepness, so a lightning surge current of 10 kA with 1 μs front is assumed (as in the similar 2070 question). On the 300 Ω line its steepness is S=10×300/1=3000S = 10 \times 300 / 1 = 3000 kV/μs.
  • Velocity v=300v = 300 m/μs. The transformer is treated as an open circuit (worst case).

Step 1: Arrester rating and protective level

Vrating=0.8×420=336 kV (rms)Vp=PR×Vrating=3×336=1008 kV\begin{aligned} V_{rating} &= 0.8 \times 420 = 336\ \text{kV (rms)} \\ V_p &= PR \times V_{rating} = 3 \times 336 = 1008\ \text{kV} \end{aligned}

Step 2: BIL of the transformer

BIL=TPR×Vp=1.25×1008=1260 kV\text{BIL} = TPR \times V_p = 1.25 \times 1008 = 1260\ \text{kV}

The next standard level, 1300 kV, would be chosen in practice.

Step 3: Maximum distance

Voltage at an open-circuited transformer a distance LL from the arrester:

Vt=Vp+2SLvV_t = V_p + \frac{2SL}{v}

Coordination requires Vt≤BILV_t \le \text{BIL}:

1008+2×3000×L300≤126020L≤252Lmax=12.6 m\begin{aligned} 1008 + \frac{2 \times 3000 \times L}{300} &\le 1260 \\ 20L &\le 252 \\ L_{max} &= 12.6\ \text{m} \end{aligned}

(With the standard BIL of 1300 kV: Lmax=292/20=14.6L_{max} = 292/20 = 14.6 m.)

At the 30 m shown in the figure: Vt=1008+20×30=1608V_t = 1008 + 20 \times 30 = 1608 kV >1260> 1260 kV, so the arrester is too far away.

Note on the 350 Ω transformer impedance

If the 350 Ω shown for the transformer is used literally, the coefficients at the transformer are

α=2×350300+350=1.077,β=350−300650=0.077\alpha = \frac{2 \times 350}{300 + 350} = 1.077, \quad \beta = \frac{350 - 300}{650} = 0.077

and the transformer voltage cannot exceed about αVp=1085.5\alpha V_p = 1085.5 kV, which is below the BIL at any distance. Real transformer windings have surge impedances of several thousand ohms, so the open-circuit (β ≈ 1) case above is the one used for design.

Answer: BIL = 1260 kV (choose 1300 kV standard); maximum arrester–transformer distance ≈ 12.6 m for the assumed 3000 kV/μs surge (30 m is not acceptable).