- 2071 Bhadra · 8 marks
Transformer BIL and maximum arrester distance
Short answer
Transformer BIL = 1.25×1008 = 1260 kV (standard 1300 kV). Using assumed surge steepness 3000 kV/μs, maximum distance L = (1260-1008)×300/(2×3000) = 12.6 m to limitt transformer voltage to BIL.
A 400 kV line shown in figure below is effectively grounded which is protected by L.A. with PR = 3. The transformer has its protection ratio (TPR) = 1.25 with Zc = 350 Ω. Determine BIL of Tr. Also find the maximum distance between transformer and lightning arrestor so that the insulation co-ordination is properly met. [Figure: 400 kV surge travelling on a line of Z0 = 300 Ω reaches an arrester connected to ground; the transformer (Z0 = 350 Ω) is 30 m beyond the arrester; α and β mark the transmitted and reflected waves at the transformer]
The transformer BIL is fixed from the arrester protective level and the transformer protective ratio. The maximum separation is then the distance at which the extra voltage built up between arrester and transformer just uses up the margin between BIL and the arrester protective level.
Assumptions
- Highest system voltage of a 400 kV system = kV (line-to-line, rms).
- Effectively grounded system: coefficient of earthing 0.8, so arrester rating = 80% of highest system voltage.
- "PR = 3" of the arrester is the ratio of its protective level (peak) to its rated voltage (rms).
- The figure gives no surge steepness, so a lightning surge current of 10 kA with 1 μs front is assumed (as in the similar 2070 question). On the 300 Ω line its steepness is kV/μs.
- Velocity m/μs. The transformer is treated as an open circuit (worst case).
Step 1: Arrester rating and protective level
Step 2: BIL of the transformer
The next standard level, 1300 kV, would be chosen in practice.
Step 3: Maximum distance
Voltage at an open-circuited transformer a distance from the arrester:
Coordination requires :
(With the standard BIL of 1300 kV: m.)
At the 30 m shown in the figure: kV kV, so the arrester is too far away.
Note on the 350 Ω transformer impedance
If the 350 Ω shown for the transformer is used literally, the coefficients at the transformer are
and the transformer voltage cannot exceed about kV, which is below the BIL at any distance. Real transformer windings have surge impedances of several thousand ohms, so the open-circuit (β ≈ 1) case above is the one used for design.
Answer: BIL = 1260 kV (choose 1300 kV standard); maximum arrester–transformer distance ≈ 12.6 m for the assumed 3000 kV/μs surge (30 m is not acceptable).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Arrester with 1000 kV BIL on 350 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- BIL and LA coordination for 10 kA discharge · High Voltage Engineering, chapter 4
- Arrester with 1000 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester with 1600 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Coordination with residual voltage 200 Id^0.25 (PR 1.2) · High Voltage Engineering, chapter 4 · asked 2×
- CT ratio for 33/6.6 kV star/delta (400/5) · Switchgear and Protection, chapter 7
- 400 km line at UPF: Zc, propagation, regulation · Power System Analysis I, chapter 5
- Merz-Price: protected winding (13.8 kV) · Switchgear and Protection, chapter 7 · asked 2×
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×