Coordination with residual voltage 200 Id^0.25 (PR 1.2)

Short answer

Residual voltage Vd = 200 × 24^0.25 = 442.7 kV. Protective ratio PR = BIL / Vd = 500 / 442.7 = 1.13, which is less than required 1.2. Therefore, the transformer is not properly coordinated.

A transformer is protected by an arrester at the incoming line. The BIL withstand voltage of the transformer is chosen to be 500 kV. The protective ratio required for transformer protection is 1.2. A lightning strike at the arrester causes an arrester discharge current of 24 kA. Check whether the transformer is properly coordinated. Assume arrester residual voltage to be given by 200 Id^0.25.

The transformer is properly coordinated if the arrester residual voltage at the given discharge current is low enough to give the required protective ratio:

PR=BILVd≥1.2PR = \frac{\text{BIL}}{V_d} \ge 1.2

Residual voltage at 24 kA

Vd=200 Id0.25=200×240.25240.25=24=4.899=2.2134Vd=200×2.2134=442.7 kV\begin{aligned} V_d &= 200\,I_d^{0.25} = 200 \times 24^{0.25} \\ 24^{0.25} &= \sqrt{\sqrt{24}} = \sqrt{4.899} = 2.2134 \\ V_d &= 200 \times 2.2134 = 442.7\ \text{kV} \end{aligned}

Protective ratio

PR=500442.7=1.129PR = \frac{500}{442.7} = 1.129

Check

  • Maximum allowed residual voltage =500/1.2=416.7= 500/1.2 = 416.7 kV.
  • Actual Vd=442.7V_d = 442.7 kV > 416.7 kV.
  • Achieved PR=1.13<1.2PR = 1.13 < 1.2.

The transformer is NOT properly coordinated.

The largest discharge current for which coordination holds is

Id=(416.7200)4=18.8 kAI_d = \left(\frac{416.7}{200}\right)^4 = 18.8\ \text{kA}

Remedies

  • Raise the BIL to at least 1.2×442.7=5311.2 \times 442.7 = 531 kV (standard 550 kV).
  • Use an arrester with a lower residual voltage.
  • Reduce the stroke current reaching the arrester with better shielding and footing resistance.

Answer: VdV_d = 442.7 kV and PR = 1.13 < 1.2, so the transformer is not properly coordinated.