Arrester coordination for 8000 kV strike
Short answer
Solve 2Vw=Vd+Id Z with Z=400 ohm and Vd=163.71 Id^0.263; discharge current is 38.93 kA, residual 428.9 kV. Protective ratio is 1.166, below 1.2, so coordination fails.
A 132 kV line is terminated by transformer and is protected by an arrester of rating 120 kV located at the incoming line. The BIL withstand voltage of the transformer is chosen to be 500 kV. The protective ratio of transformer is 1.2. Check whether the transformer is properly coordinated with the arrester if a lightning strike of 8,000 kV incident at the arrester.
| Discharge current | Residual voltage |
|---|---|
| 10 kA | 300 kV |
| 20 kA | 360 kV |
The arrester is at the end of the line, next to the transformer. When it conducts, the line's Thevenin equivalent is behind , so
The surge impedance of the line is not given. A typical 132 kV overhead line value, , is assumed.
Arrester characteristic
From the two table points:
So (kV, kA).
Discharge current and residual voltage
Solving by trial (or iteration):
| (kA) | (kV) | (kV) |
|---|---|---|
| 38.0 | 426.2 | 15 626 |
| 38.93 | 428.9 | 16 000 ✓ |
| 40.0 | 432.0 | 16 432 |
So kA and kV.
Protective ratio
Required , which means kV. Since kV, i.e. :
The transformer is NOT properly coordinated with this arrester for an 8000 kV incident surge.
Notes
- For kV the arrester current must be at most kA. That needs . So for any usual line surge impedance (about 300–400 Ω, i.e. below 447 Ω) the result is the same: not coordinated. With , kA and .
- Remedy: choose a transformer BIL of at least kV (standard 550 kV), or use an arrester with a lower residual voltage.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Arrester coordination for 40 kA discharge · High Voltage Engineering, chapter 4 · asked 2×
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- Coordination with residual voltage 200 Id^0.25 (PR 1.2) · High Voltage Engineering, chapter 4 · asked 2×
- Coordination with residual voltage 200 Id^0.25 (PR 1.25) · High Voltage Engineering, chapter 4 · asked 2×
- Arrester 100 m from transformer coordination · High Voltage Engineering, chapter 4
- Arrester current, resistance and rating on 132 kV line · High Voltage Engineering, chapter 4
- 4.2 kV/120 V transformer voltage regulation · Electrical Machines, chapter 2
- CT ratio and connection for 11/132 kV · Switchgear and Protection, chapter 7
- Voltage ratio transfer function, port 2 terminated by 2 H · Electrical Circuit Theory, chapter 5
- Ratio of vertical separation, 132 vs 220 kV · Transmission and Distribution System Design, chapter 4