Arrester coordination for 8000 kV strike

Short answer

Solve 2Vw=Vd+Id Z with Z=400 ohm and Vd=163.71 Id^0.263; discharge current is 38.93 kA, residual 428.9 kV. Protective ratio is 1.166, below 1.2, so coordination fails.

A 132 kV line is terminated by transformer and is protected by an arrester of rating 120 kV located at the incoming line. The BIL withstand voltage of the transformer is chosen to be 500 kV. The protective ratio of transformer is 1.2. Check whether the transformer is properly coordinated with the arrester if a lightning strike of 8,000 kV incident at the arrester.

Discharge currentResidual voltage
10 kA300 kV
20 kA360 kV

The arrester is at the end of the line, next to the transformer. When it conducts, the line's Thevenin equivalent is 2Vw2V_w behind ZZ, so

2Vw=Vd+IdZ,Vd=kIdβ2V_w = V_d + I_dZ, \qquad V_d = kI_d^{\beta}

The surge impedance of the line is not given. A typical 132 kV overhead line value, Z=400 ΩZ = 400\ \Omega, is assumed.

Arrester characteristic Vd=kIdβV_d = kI_d^{\beta}

From the two table points:

360300=(2010)β  ⇒  β=ln⁡1.2ln⁡2=0.2630k=300100.2630=163.71\begin{aligned} \frac{360}{300} &= \left(\frac{20}{10}\right)^{\beta} \;\Rightarrow\; \beta = \frac{\ln 1.2}{\ln 2} = 0.2630 \\ k &= \frac{300}{10^{0.2630}} = 163.71 \end{aligned}

So Vd=163.71 Id0.263V_d = 163.71\,I_d^{0.263} (kV, kA).

Discharge current and residual voltage

2×8000=163.71 Id0.263+400 Id2 \times 8000 = 163.71\,I_d^{0.263} + 400\,I_d

Solving by trial (or iteration):

IdI_d (kA)VdV_d (kV)Vd+400IdV_d + 400I_d (kV)
38.0426.215 626
38.93428.916 000 ✓
40.0432.016 432

So Id=38.93I_d = 38.93 kA and Vd=428.9V_d = 428.9 kV.

Protective ratio

PR=BILVd=500428.9=1.166PR = \frac{\text{BIL}}{V_d} = \frac{500}{428.9} = 1.166

Required PR=1.2PR = 1.2, which means Vd≤500/1.2=416.7V_d \le 500/1.2 = 416.7 kV. Since 428.9>416.7428.9 > 416.7 kV, i.e. 1.166<1.21.166 < 1.2:

The transformer is NOT properly coordinated with this arrester for an 8000 kV incident surge.

Notes

  • For Vd=416.7V_d = 416.7 kV the arrester current must be at most Id=(416.7/163.71)1/0.263=34.87I_d = (416.7/163.71)^{1/0.263} = 34.87 kA. That needs Z≥(16000−416.7)/34.87=447 ΩZ \ge (16000 - 416.7)/34.87 = 447\ \Omega. So for any usual line surge impedance (about 300–400 Ω, i.e. below 447 Ω) the result is the same: not coordinated. With Z=300 ΩZ = 300\ \Omega, Id=51.8I_d = 51.8 kA and PR=1.08PR = 1.08.
  • Remedy: choose a transformer BIL of at least 1.2×428.9=5151.2 \times 428.9 = 515 kV (standard 550 kV), or use an arrester with a lower residual voltage.

✓ Answer checked by Claude Opus 5.5 (high effort)